APPLICATION 

 

They are suitable for waste water, industrial applications, agricultural purposes, for viscous e dense liquids. 
Temperature:   min -10˚ C max 70˚ C 
Pressure:  

DN 25 – 150 16 Bar 
DN 200 – 500 10 Bar 

Note: Please ensure the choice of the corresponding item 

 

 

4.

 

ASSEMBLY   

 

-

 

Handle with care; 

-

 

Place  the  valve  between  the  flanges  of  the  pipe  and  install  the  seal  between  the  pipe  and  valve 

flanges.  Check  that  the  seals  have  been  positioned  correctly.  The  distance  between  the  counter 
flanges must be the equal to the valve’s face to face distance. Do not use bolts of the counter flanges 
to bring the piping close to the valve. The bolts should be cross tightened; 

-

 

Do not weld the flanges to the piping after installing the valve; 

-

 

Water  hammers  might  cause  damage  and  ruptures.  Inclination,  torsions  and  misalignments  of  the 

piping may subject the installed valve to excessive stresses. It is recommended that elastic joints be 
used in order to reduce such effects as much as possible; 

-

 

 

Use belts and safety hooks for harnessing and lifting (see picture 1). 

 
This valve is unidirectional: install in accordance with the flow direction arrow indicated 
on the body. 

 
 
 
 
 
 
 
 
 
 

 
 
 

Piping with vertical upstream flow: install the valve as shown in figure 3. 

 
 
Piping with horizontal or inclined flow (upstream flow): install the valve as shown in figure 4. 

 
 