Smart Connect Multi-loop Repeater Installation Manual

 

 
www.zetaalarmsystems.com

 

 
 
 

Cable Grounding 

 
The Repeater has no internal earth bars. It is recommended that network wiring is connected to ground at a Smart Connect control 
panel (only one side of the network wiring should be grounded). 

 

DC Power Wiring  

 
The SMART/REP needs to be powered by a 28VDC external EN54 approved power supply. The cables used for this must be fire rated. 
 

Recommendations 

The DC supply to the Repeater should be fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and 2.5mm²), or equivalent. 
The AC supply to the PSU should be fed from an isolating double (or single) pole switch fused spur, and fused at 5A. This should be 
secure from unauthorized operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’. The supply must be exclusive to the repeater.  
 

Connecting the DC Power 

The incoming DC power cable should be kept separate from the RS485 network cables to help minimise interference. 

 
 

 
 
 
It is advisable to apply power to the repeater before connecting any network cables, to check for correct operation, and to familiarise 
yourself with the repeater panels’ controls. 
 
If a knockout is removed, fill the hole with a suitable cable gland. If any knockout is removed, but subsequently not used, it should be 
covered up. 
 

Figure 2: Termination PCB Layout  
 

 

 

ATTENTION: 

MAKE SURE ANY SPARE ENTRY HOLES THAT HAVE BEEN OPENED, BUT NOT USED ARE COVERED WITH 

SUITABLE GROMMETS OR BLANKING SCREWS. 

ATTENTION: 

DO NOT DRILL ANY ENTRY HOLES INTO THE DOOR SECTION OF THE ENCLOSURE. 

(Not used) 

Summary of Contents for Smart Connect Multi-loop

Page 1: ...GLT 261 7 3 Doc GLT 261 7 1 Issue W I P Date 25 08 2018 Doc GLT 261 7 12 Issue 001 Date 08 02 2021 MULTI LOOP REPEATER Installation Manual...

Page 2: ...Panel Installation and Dimensions 5 Enclosure Dimensions 5 Panel Construction Details 5 Locating the Fire Alarm Control Panel 5 Mounting the Enclosure 6 Mounting Hole Dimensions 6 Planning Cable Entry...

Page 3: ...all control panel electronic hardware system memory components and the system program A hardware watchdog circuit is provided to ensure that System programs are functioning properly If a problem devel...

Page 4: ...4 Typical Smart Network Fire Alarm Wiring System Components Display PCB MMP DSP 4 3 colour touch screen display 32 bit microcontroller MCU USB connection to PC software 2 key switch inputs Termination...

Page 5: ...9005 Black Leatherette The repeater enclosure can be semi flushed into a wall or surface mounted Locating the Fire Alarm Control Panel The control panel should be installed per BS5839 1 2017 recommend...

Page 6: ...8 roundhead or countersunk woodscrews or similar Remove any debris from the enclosure Take care not to damage the panel during installation Mounting Hole Dimensions Fig 1 Planning Cable Entry The Knoc...

Page 7: ...r and fused at 5A This should be secure from unauthorized operation and be marked FIRE ALARM DO NOT SWITCH OFF The supply must be exclusive to the repeater Connecting the DC Power The incoming DC powe...

Page 8: ...Smart Connect Multi loop Repeater Installation Manual www zetaalarmsystems com 8 Figure 3 28V DC wiring Figure 4 28V DC terminal wiring ATTENTION CHECK POLARITY IS CORRECT BEFORE TURNING THE POWER ON...

Page 9: ...turn off Power LED will blink a few times c LCD will show touch for calibration Press the screen within 3 seconds to perform a screen calibration The screen is calibrated at the factory so this step...

Page 10: ...stance Between Nodes 1KM with screened data cable 100M using a standard fireproof cable Communication Protocol RS485 Network Wiring Typologies Bus or Ring BS 5839 1 2017 requires that network cable be...

Page 11: ...using a standard fireproof cable Network Wiring Typologies Bus Ring recommended Software Maximum Event Log 8032 Events Software Programming Touchscreen LCD Display LCD 4 3 Resistive touch screen 480 x...