PREMIER M PLUS USER MANUAL & MAINTENANCE GUIDE  

 

Approved Document No: GLT.MAN-112 

 

PAGE 12

 

Issue: 2.3      Author: NRPJ         Date: 25/5/2017 

8. USING SOUNDER DELAYS 

 

8.1 WHAT IS A SOUNDER DELAY 

 

In certain circumstances it may be desirable to have a delay between the panel detecting a fire, and starting its external sounders, to 
allow the responsible person to check the cause of the alarm, to stop building evacuation by an obvious false alarm.  If the cause of 
the  Alarm  is  found  to  be  a  true  fire  hazard,  the  Delay  can  be  overridden  and  the  Alarm  Sounders  activated  immediately.  
Alternatively, in the case of a false alarm, the Panel can be reset. 
 

8.2 SOUNDER DELAY SETTING 

 
On the PREMIER M PLUS panel, the sounder delay is global. That is, all zones will be delayed by the same amount. If a delay is used, 
it will have been set by the installer to between 1 minute and 9 minutes. The user can toggle the delay on or off be enabling controls 
and pressing Sounder Delay button. To change the delay time, contact the system installer. 
 

8.3 HOW THE PANEL INDICATES SOUNDER DELAY  

 
If a Delay has been programmed into the Panel, the SOUNDER DELAY LED will be lit.  When a zone processes an alarm signal, the 
panel will indicate fire in the usual way, but the sounders will not be active until the delay period has expired.  To override this delay, 
press Sounder Delay button, which will cause the external sounders to energise. If there is no delay programmed, the Sounder Delay 
button has no function. 
 

8.4 A FIRE ALARM CONDITION ON A DELAYED PANEL 

 
When an alarm occurs on a Delayed Panel, the panel will: - 
 

 

Light its General Fire and appropriate Fire Zone light(s). 

 

Sound its Internal buzzer. 

 

Turn on the F.A.R.E. Output. 

 

Start the Delay countdown sequence. 

 

Wait until the end of the delay, then start the sounders. 

 
 

 

8.5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE ALARM  

 
If on investigation the cause of the Alarm is found to be a true fire hazard, pressing the Sounder Delay button, will active the Alarm 
Sounders and Outputs with immediate effect.  
 

8.6 RESET THE SYSTEM IN THE EVENT OF A FALSE ALARM 

 
If, on investigation, the cause of  the  Alarm is found to  be false,  turn the Key switch to the “Controls Enabled”  position and  press 
reset button. 
 
 

8.7 TO TURN OFF THE SOUNDER DELAY 

 
The user can toggle the delay on or off by enabling controls and pressing sounder delay button. To permanently turn off the delay, 
contact the system installer. 
 

Summary of Contents for Premier M plus

Page 1: ...PREMIER M PLUS USER MANUAL MAINTENANCE GUIDE Approved Document No GLT MAN 112 Issue 2 3 Author NRPJ Date 25 5 2017 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE...

Page 2: ...ire extinguishers if suitably trained or call the fire brigade IF IN DOUBT CALL THE FIRE BRIGADE To reset the panel press the reset button If the panel goes back into alarm silence the sounders and ca...

Page 3: ...LARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL...

Page 4: ...de called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point The system is split into Zones each covering...

Page 5: ...operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the PREMIER M PLUS Range of Fire Alarm Panels we recommend the follow...

Page 6: ...ch may have been programmed into the Panel by pressing the Sounder Delay button Putting the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid una...

Page 7: ...ONLY STEADY RED A manual evacuation has occurred The sounders will be active COMMON FIRE ZONE FIRE F A R E ACTIVE STEADY RED STEADY RED STEADY RED A fire has occurred in the zone indicated The sounde...

Page 8: ...ilenced by turning the control key to Control Enable position and momentarily pressing the Start Stop button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red...

Page 9: ...a new glass element if glass type If the cause of the alarm was by detector activation e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel...

Page 10: ...lt zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared It can take up to 60 seconds from repairing a fault for the display to clear Short Circuit Fault If...

Page 11: ...he panel On power up the panel looks for a signal from a repeater If it does not see one it assumes there is no repeater connected If the panel sees a repeater but then looses its signal it will show...

Page 12: ...ash fast This means the panel is in disable enable mode 3 Press scroll switch once and this will cause the General Disablement LED Zone1 fault and Zone 1 Disablement to flash with a 3 quick flash then...

Page 13: ...the SOUNDER DELAY LED will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To overrid...

Page 14: ...te 25 5 2017 User Manual Modification History Do Not Print this Page when creating PDF Of the manual ISSUE DATE CHANGES 2 1 10 11 2010 Version Before addition of modification History 2 2 23 7 2012 Dra...

Reviews: