PREMIER M PLUS USER MANUAL & MAINTENANCE GUIDE  

 

Approved Document No: GLT.MAN-112 

 

PAGE 11

 

Issue: 2.3      Author: NRPJ         Date: 25/5/2017 

7. DISABLEMENTS 

 

7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM. 

 
Certain  parts of this Fire  Alarm  Panel can  be temporarily  disabled (i.e. switched off) to suit  prevailing conditions.  For  example, if 
there is a risk of a False Alarm in a zone, for example, an area full of dust  because of building  work, it is possible for the user  to 
disable that zone during the risk period and then enable it again afterwards.  During a disablement of a zone(s), no fire or fault signal 
will be processed for that zone(s).  Only zone(s) in a non-alarm state can be disabled, that is zones already in fire cannot be disabled. 
 
External sounders can also be disabled as could be required in certain conditions. 
 

7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS. 

 

1.

 

Turn control key to “Controls Enable” position; 

2.

 

Press FUNCTION switch momentarily, this will cause General Disablement LED to flash (fast).  This means the panel is in 
disable/enable mode; 

3.

 

Press  scroll  switch  once  and  this  will  cause  the  General  Disablement  LED,  Zone1  fault,  and  Zone  1  Disablement  to  flash 
(with a 3 quick flash, then off pattern); 

4.

 

Press SELECT to disable this zone, or SCROLL to move to another zone; 

5.

 

The scroll order is Detection Zone 1-24 (Zone fault & zone disabled LEDs on), then Common Sounders, Then F.A.R.E. circuit. 

6.

 

Select zone to be disabled.  The LEDs will now flash 3 quick flashes, then ON. This shows that this zone has been disabled. 

7.

 

Switch controls key to off position, then both the  disabled Zone Disablement LED and the General Disablement LED will 
remain lit (steady. 

 

7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS. 

 

1.

 

Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED with stay 
lit (steady); 

2.

 

Press FUNCTION followed by SCROLL. Zone 1 LEDs will flash 

3.

 

Press scroll switch until the LEDs are flashing at the disabled zone; 

4.

 

Press “SELECT” and this will cause the General Disablement LED to flash (with a 3 quick flash, then off pattern); 

5.

 

Turn control Key to “Off” position and this will turn off the General Disablement and Zone Disablement LEDs. 

 
 

Summary of Contents for Premier M plus

Page 1: ...PREMIER M PLUS USER MANUAL MAINTENANCE GUIDE Approved Document No GLT MAN 112 Issue 2 3 Author NRPJ Date 25 5 2017 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE...

Page 2: ...ire extinguishers if suitably trained or call the fire brigade IF IN DOUBT CALL THE FIRE BRIGADE To reset the panel press the reset button If the panel goes back into alarm silence the sounders and ca...

Page 3: ...LARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL...

Page 4: ...de called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point The system is split into Zones each covering...

Page 5: ...operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the PREMIER M PLUS Range of Fire Alarm Panels we recommend the follow...

Page 6: ...ch may have been programmed into the Panel by pressing the Sounder Delay button Putting the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid una...

Page 7: ...ONLY STEADY RED A manual evacuation has occurred The sounders will be active COMMON FIRE ZONE FIRE F A R E ACTIVE STEADY RED STEADY RED STEADY RED A fire has occurred in the zone indicated The sounde...

Page 8: ...ilenced by turning the control key to Control Enable position and momentarily pressing the Start Stop button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red...

Page 9: ...a new glass element if glass type If the cause of the alarm was by detector activation e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel...

Page 10: ...lt zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared It can take up to 60 seconds from repairing a fault for the display to clear Short Circuit Fault If...

Page 11: ...he panel On power up the panel looks for a signal from a repeater If it does not see one it assumes there is no repeater connected If the panel sees a repeater but then looses its signal it will show...

Page 12: ...ash fast This means the panel is in disable enable mode 3 Press scroll switch once and this will cause the General Disablement LED Zone1 fault and Zone 1 Disablement to flash with a 3 quick flash then...

Page 13: ...the SOUNDER DELAY LED will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To overrid...

Page 14: ...te 25 5 2017 User Manual Modification History Do Not Print this Page when creating PDF Of the manual ISSUE DATE CHANGES 2 1 10 11 2010 Version Before addition of modification History 2 2 23 7 2012 Dra...

Reviews: