PREMIER AD INSTALLATION MANUAL.  

 

 

Software:PANEL:R1107 & LOOP:R1062 

   

Approved Document No: GLT.MAN-105A

 

 

 

 

PAGE 25

 

Issue : 2.02         Authorised: GH      Date: 16/07/2007 

14. TEST MODE 

 

14.1 WHY USE TEST MODE 

 

To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is 
available. 

 

When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for 
approximately eight seconds on and four seconds off.  This cycle continues until the cause of the 
Alarm is removed (either by the test smoke clearing from the detector or the manual call point being 
reset), sounders will then stop activating. 

 

Should an Alarm occur on a zone that is not programmed to test, the Fire Alarm Panel will cancel the 
test mode. After the cause of the alarm has been checked, and the panel reset, test mode will have 
to be selected again to resume testing. 

 

14.2 TO PROGRAMME ZONE IN TEST MODE 

 

NOTE:  Only 

one zone

 can be programmed in test at any one time. 

 

1.  Insert and turn control key to enabled position; 

 

2.  Press TEST Button. The screen will prompt for the test code 

 

3.  Enter the Test code 

2 4 8.

 

 

4.  The screen will now show Test Mode. 

 

5.  Press TEST FUNCTION SELECT button to select the zone to be  
 tested. 

 

 

6.  Press CONFIRM to enter test mode for this zone 
 

The General Test and Zone Test LEDs will now be lit. 

 

7.  Detectors in this zone can now be tested with smoke spray. The  
 

sounders will operate for about 4 seconds, then they will reset. This 

 

cycle will continue until all smoke spray has cleared from the detector. 

 

8.  Once testing of that zone is completed, press TEST FUNCTION SELECT button to move to 

another Zone or turn the control key switch to off position to exit test mode. 

 

14.3 TO PROGRAM SOUNDER CIRCUITS IN TEST MODE 

 

NOTE:  Only 

one sounder circuit or the loop sounders

 can be in test mode at any one time.  

NOTE:  Only the ADDRESSABLE SOUNDERS can be tested with the loop sounder one man 
test mode. The ASSOCIATED SOUNDER BASES cannot be tested this way because of their 
slower stop/start time.

 

 

1.  Insert and turn control key to enabled position; 

 

2.  Press TEST Button, The screen will prompt for the test code. 
 

Enter the code 2 4 8. 

 

3.  The screen will now show Test Mode, Zone 1, Normal Operation. 

 

4.  Press TEST FUNCTION SELECT button to select the sounder  

 

 

to be tested.  

 

5.  Press confirm to enter test mode for this function. The LED will  
 

now be on steady. 

 

6.  The Sounders will now pulse 3 seconds on, 3 seconds off until  
 

they are taken out of test mode. This allows all the sounders 

 

to be tested for correct operation, and dB output. 

 

7.  Once testing of that sounder circuit is completed, press  
 

TEST FUNCTION SELECT button to move to another circuit, or  

 

turn the control key switch to off position to exit test mode 

 

To test associated sounder bases, use the stop/start sounder button (evacuate). Note that the 
sounders will take up to 9 seconds to start. 

 

***NOTE***Associated sounder bases are controlled by the detector. 

Removing the detector will 

leave the sounder base inoperative. 

     Test Mode 
      Zone  1 

 

  Normal Operation 

 Enter Access Code    

          

  

        

 

     Test Mode 
      Zone  2 

 

    Test Active 

     Test Mode 

      Zone  1 
 

  Normal Operation 

 Enter Access Code    

          

  

        

 

     Test Mode 

 External Sounder 1   
 

    Test Active 

Summary of Contents for Premier AD

Page 1: ...INSTALLATION MANUAL...

Page 2: ...OCIATED SOUNDER BASES 15 8 4 SUPPORTED SOUNDER TYPES THEIR APPLICATIONS 15 9 AUXILIARY INPUTS OUTPUTS 16 9 1 AUXILIARY INPUT WIRING EXAMPLES 16 9 2 AUXILIARY OUTPUT WIRING VOLTAGE FREE CHANGEOVER CONT...

Page 3: ...ith our instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 20...

Page 4: ...The screen is simply there to identify loop device fault locations and to help in setting up the panel 2 2 ADVANTAGES OF AN ADDRESSABLE FIRE ALARM SYSTEM The table below lists the main advantages of a...

Page 5: ...elow Old CPU 3 large ICs New CPU 2 small surface mount ICs If the control panel has the OLD CPU card then some of the options in this manual will not be applicable Contact your supplier to obtain Vers...

Page 6: ...op sounders address 113 to 126 which allows 14 devices Each option has advantages disadvantages Check the Sounder option chart on page 15 for information 3 If zonal sounder operation is required loop...

Page 7: ...ire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resisting...

Page 8: ...oved by a push from inside the control panel box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c...

Page 9: ...s connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE...

Page 10: ...nder A maximum of 32 loop powered addressable sounders or sounder bases are permitted on the loop On the Premier AD Panel all Sounder Bases are always configured as common sounders Short circuit isola...

Page 11: ...L2 L 1 I O U T L1IN R C RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals are marked in...

Page 12: ...Base 80 090 FE IB Fyreye Addressable Loop Isolator Base 80 100 FEA SB Fyreye Addressable Sounder Base 80 101 FEA ISB Fyreye Addressable Isolator Sounder Base 43 305 ZT CP2 AD Zeta Addressable EN54 Cal...

Page 13: ...at during an alarm condition maximum current draw the voltage at all detectors must be at least 17 Volts with at least 5V of superimposed data signal The exact calculation equations are beyond the sco...

Page 14: ...N 3 OFF 2 ON 1 OFF As an alternative to using this chart use the table on the following page SW 4 3 2 1 OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O 1111 LOOP 1 LOOP 2 SW...

Page 15: ...off off on on on 46 on off off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off of...

Page 16: ...on any alarm Note that the Premier AD has a preset time out of 3 minutes after which ALL loop sounders will start even one from a different zone 8 3 ASSOCIATED SOUNDER BASES Associated sounder bases...

Page 17: ...wiring options CLASS CHANGE 2nd Fire Alarm AUX FIRE RELAY CM NO CLASS CHANGE The termination for the above inputs must be as indicated on the main PCB See page 15 The Earthing of the cable screens sho...

Page 18: ...wer supplies The panel supports up to 4 repeaters Connections Premier AD Termination PCB AD Repeater SERIAL REPEATER COM SERIAL REPEATER COM AUX SUP 28V AUX SUP 0V 11 2 SERIAL PRINTER CONNECTION The P...

Page 19: ...o configure the loops The panel displays configuration in progress Please wait It will return to Configuration Menu 2 when completed 7 Press PREVIOUS button followed by button 1 to view the loop conte...

Page 20: ...s shown below Note if every detector has a sounder base or if most of the detectors have a sounder base this speed up operation will have little or no effect 1 Press enter NEXT followed by 369 to ente...

Page 21: ...rm Fault Description If the device is in a fault condition a description of the fault will appear here It will show one of the following messages FAULT MEANING Changed The device had been changed with...

Page 22: ...vent number the date the time the type of event in this case a DEVICE ALARM and the Zone loop and address if appropriate Next Previous buttons will cycle through the list Faults Selecting this option...

Page 23: ...ximum value of 524287 and will return to 0 after this 12 8 CHECKING SOFTWARE VERSION The Premier AD now has the ability to view the software version from the screen From Configuration menu 2 select co...

Page 24: ...y along with the GENERAL DISABLEMENT LED This section is now disabled NOTE Call points in this zone will still be active To disable the call points as well disable them individually as points see 13 3...

Page 25: ...re one or more disabled points in this zone the screen will show TIP a quick way to enable several disabled points is to disable the zone then re enable it To view from the Device Status screen press...

Page 26: ...til all smoke spray has cleared from the detector 8 Once testing of that zone is completed press TEST FUNCTION SELECT button to move to another Zone or turn the control key switch to off position to e...

Page 27: ...ssing device and check if it has its LED on Detector or check the dip switch setting 4 If this does not cure all double addresses go to the known location and temporarily remove the device The panel w...

Page 28: ...hing is shorting to earth usually through the cable screen Disconnect the earth screens one at a time to determine the problem line Note connecting other equipment eg an oscilloscope to the panel can...

Page 29: ...10 LOOP WIRING FAULTS A loop fault can be caused by a break or short circuit in the Loop wiring Open the panel and look for the 4 green LEDs on the termination PCB Under normal conditions these should...

Page 30: ...Input Output Unit ZIOU 2 2 10 16 32 Zeta Sounder Control Module ZSCC 2 2 10 16 32 Zone Monitor Unit ZT ZM 6 8 30 22 10 20 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c...

Page 31: ...al Example A system comprises of 160 Addressable Optical detectors 64 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required T...

Page 32: ...t to loop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault...

Page 33: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY...

Reviews: