PREMIER AD INSTALLATION MANUAL.
Software:PANEL:R1107 & LOOP:R1062
Approved Document No: GLT.MAN-105A
PAGE 19
Issue : 2.02 Authorised: GH Date: 16/07/2007
caps lock as necessary.
10. Press enter when the label has been entered.
11. To skip many addresses, or to change loop, it is
possible to select the next loop and address to edit.
Press button 1 or 2 to select the new loop. The Panel
will then prompt for the address. Type the address and
press enter. The panel will now jump to this address.
The sounder symbol in the top right hand corner shows that this detector might have
an “associated sounder base” connected. The panel will send the “activate base
sounder” command to this address in the event of an alarm. See Sounder section &
Sounder base setup for further information.
12. When all devices have been entered, press Cancel to exit the message editing
screen, and cancel again to exit the menu and to return to normal.
The panel is now configured and ready for operation.
12.2 CONFIGURING THE SOUNDER BASES
On the Premier AD, all detectors are treated as if they have a sounder base during
the initial configuration. If a loop contains a large number of detectors, and a small
number of sounder bases, then the sounders might take a long time (between 4 & 8
seconds) to start.
If this scenario exists, it is possible to speed up operation as shown below. (Note: if
every detector has a sounder base, or if most of the detectors have a sounder base
this “speed up operation” will have little or no effect.
1. Press enter, NEXT, followed by 369 to enter
Configuration Menu 2. Select option 5 to edit device status.
Select a detector that does NOT have a sounder base
attached.
2. Press the Disablement SELECT button. The sounder
symbol turns off to show that this detector no longer has
an associated sounder. (Pressing select again will
continue to toggle the sounder on & off.)
3. Repeat for all detectors that do not have an associated sounder base fitted.
12.3 SETTING TIME AND DATE
To set the time & date, enter Configuration Menu 2 and select Configure System (6).
The System Menu is now displayed. Select option 1 to set time & date. Enter the
Day, Month, Year, Hour & Minutes as prompted, and press enter to save, or Cancel
at any time to exit.
12.4 SETTING A CUSTOM BANNER
On the Premier AD, the default screen shows Fire alarm Panel to EN54. But this can
be changed to any 2 lines of 20 Characters that are required. In the System Menu,
type
NaMe
(Caps lock,
N
,Caps lock,
a
,Caps lock,
M
,Caps lock,
e
). Then type the first
line of text, followed by enter, then the second line of text, followed by enter. This
message will now be the screen when the panel is running normally.
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Lp:1 Ad:016
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Lp:1 Ad:016
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Lp:1 Ad:016
Enter Loop Address
Loop: 1
Address: 000