INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 32
15.4 Using the event log
The ID2 has a 1000 entry event log. In the event of the log
being full, it will wrap around, and overwrite the earliest entries.
The event log can be viewed through Configuration Menu 1 by
selecting Option 3 - View Event Log. The screen prompts for which
events to display: Alarms, Faults, System or All.
Alarms
If the alarm option is shown, only alarms will be displayed. The screen
will show the event number, the date, the time, the type of event (in
this case, a DEVICE ALARM), and the Zone, and address.
Next & Previous buttons will cycle through the list.
Faults
Selecting this option will display all the faults recorded on the system,
Both device faults and general faults. The screen will show the event
number, the date, the time, the type of event (in this case, a
DEVICE CHANGED fault), and the Zone, and address,
if appropriate. Next & Previous buttons will cycle through the list.
System.
The ID2 also records other non critical items, such as
User access, clock change, configuration changed, event log erased etc. These
can be used to help determine the chain of actions before or after an event.
The types of events recorded are: - Power On/Startup, Panel Reset,
Evacuate, Access Level 2, Access Level 1, Sounders Silenced,
Configure Loops, Time & Date Set, Zone Disabled, Zone Enabled, Device Disabled,
Device Enabled, Zone Test Start, and Zone Test Finish.
Note
: during installation and commissioning, it is possible to create a large number of
events, especially if a configured Zone is disconnected. This is normal, and is not a
case for concern. These events can be cleared, using Engineer Menu 2.
To clear the event log, go to Engineer Menu 2 and select option 6 (Configure
System). Select Option 6 to go to the reset screen. Choose option 1 to reset event log.
The screen warns that this cannot be undone. Press ENTER to clear the event log, or
any other button to cancel this screen. It will also prompt for the access code (159)
Note that when the event log is cleared, the EVENT NUMBER
remains the same. This is so that a visiting engineer will have an idea
of the activity on a panel, even if the event log has been cleared. The
counter has a maximum value of 524287, and will return to 0 after this.
View Event Log
1: Alarms 4: All
2:Faults
3: System
Event 167
13-01-2007 17:21
Device Alarm
Zone:03 ID:010
Event 173
25-01-2007 17:21
Device Changed
Zone:01 ID:013
Event 174
25-01-2007 17:22
Access Level 2
Reset Settings
1: Logs
2: Zones
Clear Event Log
ENTER to Continue
Clear Event Log
WARNING: This Action
cannot be undone
ENTER to Continue
Enter Access Code