background image

Where to Install a Gas Detector

Gas Type

Molecular Weight

NH3

17

CO

28

Air

29

NO2

30

H2S

34

Propane

44

Ethanol

46

N-Butane

58

Acetone

58

Isopropyl Alcohol 

60

N-Pentane

72

Benzene

78

N-Hexane

86

Ethyl Acetate

88

Toluene

92

N-Heptane

100

N-Octane

114

Unleaded Petrol

114

Like all gas detectors, the best place to 

install a 

Gas Sense detector

 will depend on 

the target gas. In general, for gasses lighter 

than air it will be installed 30-50cm from the 

ceiling. For gasses lighter than air it will be 

installed 30-50cm from the floor. For gasses of 

a similar weight to air, the gas sense detector 

should be installed close to head height 

(approx. 1.2 to 2.0m)

The coverage of these detectors will depend on the 

target gas, and the airflow conditions in the area to be 

protected. The Typical coverage is 50m².

If the gas detector is being installed to monitor a 

specific risk, then the detector should be located 

approximately 1.5m away from that point (This is 

because if the gas escapes under pressure, it may 

be forced past the sensor, rather than into it, if the 

detector is too close).

Lighter Gases

30cm to 50cm

Heavier Gases

30cm to 50cm

Gases of Similar 

Weight to Air

1.2 to 2.0m

Environmental Factors

When choosing the best place to install the detector, 

consider all other environmental factors in that area, 

such as:-

Ventilation or Air Conditioning Vents

 – Do not place a 

detector where forced air flow will prevent gas entering 

the detector.

Open Windows

 – Airflow through an open window can 

similarly prevent gas entering the detector.

Dust & Debris

 – Avoid placing the detector where a 

constant generation of debris could block the filter, 

preventing gas from entering the sensor chamber.

Maintenance access

 – critical detectors should be 

checked regularly, and the sensor will need to be 

replaced every 3-5 years. Do not fit to an inaccessible 

location.

Ceiling beams

 – if a lighter than air gas is to be 

detected, large ceiling beams can effect coverage, 

requiring a detector between each beam.

The Gas sense range of detectors are not suitable for 

use in hazardous areas. They are intended for use in 

light industrial, academic, commercial or domestic 

installations.

4

Summary of Contents for ZS-H2S/500

Page 1: ...Gas Sense Gas Detection System...

Page 2: ...s Detector 4 When to Test the Detector 5 Detector Construction 6 Gas Sense Detectors 7 Toxic Detector Specifications 8 Combustible Detector Specification 9 10 Zeta Sense Gas Control Panel 11 Zeta Addr...

Page 3: ...build up of combustible gas caused by a leak can cause an explosion Or a build up of toxic gas such as carbon monoxide can be fatal Introduction to the Gas Sense System With this in mind Zeta Alarm S...

Page 4: ...es under pressure it may be forced past the sensor rather than into it if the detector is too close Lighter Gases 30cm to 50cm Heavier Gases 30cm to 50cm Gases of Similar Weight to Air 1 2 to 2 0m Env...

Page 5: ...sing the instrument to a known concentration of test gas The instrument reading is compared to the actual quantity of gas present as indicated on the cylinder If the instrument s response is within an...

Page 6: ...dant ABS The filter housing is made from stainless steel The detector itself has 4 control buttons to allow configuration of the unit It has a 2 x 16 character LCD display plus 4 indication LEDS to sh...

Page 7: ...ll light its relevant alarm LEDs and operate its relays They operate concurrently so that in the highest alarm level all lower alarm LEDs relays will remain ON System Mode In System mode the detector...

Page 8: ...040ppm 050ppm 060ppm 070ppm 080ppm 020ppm 025ppm 030ppm 035ppm 040ppm 0 20kppm 0 25kppm 0 30kppm 0 35kppm 0 40kppm 020ppm 025ppm 030ppm 035ppm 040ppm 4 0ppm 5 0ppm 6 0ppm 7 0ppm 8 0ppm 060ppm 075ppm 0...

Page 9: ...ld Default 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 1st Alarm LEL Bold Default 20 25 30 35 40 20 25 30 35...

Page 10: ...0 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 10 15 20 25 30 1st Alarm LEL Bold Default 20 25 30 35 40 20 25 30 35 40 20 25 30 35 40 20 25 30 35 40 20 25 30 35 40 20 25 30 35 40 20 25 30...

Page 11: ...ility is useful if there are many detectors spread across a wide area on the system The system can be divided into 20 zones allowing detectors to be grouped either by gas type or by building area The...

Page 12: ...low the outputs to be programmed whilst others will have a default pre programmed operation Model ZIOU ZIOU 230 Part No 48 105 48 106 Operating Voltage 17 33V DC 17 33V DC Quiescent Current 900uA 900u...

Page 13: ...evice address and sound output of 94 dBA at 1m Both units have a built in short circuit isolator to provide system integrity in the event of cable damage Model ZAMT R ZAMT W ZAMTF R Part No 42 007 42...

Page 14: ...Typical Connection Diagram Zeta Maxitone Sounder ZIOU Zeta Addressable Gas Sense ZSC100 Single Loop Gas Control Panel 24V PSU Mains In 14...

Page 15: ...ated on the cylinder Within the specified tolerance range If a detector fails this bump test then it should be zero s in clean air then recalibrated using the calibration cap and the gas cylinder Test...

Page 16: ...Tel 44 0 1792 455 175 Fax 44 0 1792 455 176 E mail info zetaalarmsystems com Web www zetaalarmsystems com Detection House 72 78 Morfa Road Swansea SA1 2EN United Kingdom Available now from...

Reviews: