SSG-0101                                                          ZetaAlarm Systems    

 

8

 

Fault Relay 

The  power  supply  source  is  provided  with  a  fault  relay  to  indicate 
any anomaly to a remote control unit. On idle, this relay is energized 
to  indicate  normal  operation;  if  any  fault  occurs,  it  is  immediately 
triggered except in the event of a 220 Vac mains power supply loss, 
which  is  indicated  after  a  delay  of  some  8  minutes  in  order  to 
prevent failures due to intermittent blackouts. 

 

Fault Relay Operation 

 

Connector J4 (FAULT) with three terminals 

Terminal 1 (Left) C common 
Terminal 2 (Center) NO or normally open 
Terminal 3 (Right) NC or normally closed 

 

The fault relay functions as follows: 

 

 

Stop control (no power) or indicating fault 

 

 

Between C and NC —> continuity 
Between C and NO —> circuit open 

 

 

Control in fault-free operation, i.e. NORMAL STATE 

 

 

Between C and NC  —> circuit open 
Between C and NO  —> continuity 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 

 

Summary of Contents for SSG1

Page 1: ...POWER SUPPLY SOURCES SERIES SSG SSG 1 5 SSG2 5 SSG5 Instruction Manual July 12 2006 SSG 0101 All the information contained in this document may be modified without prior warning...

Page 2: ...suitable recycling bin or return it to the supplier in the original packaging of the new batteries Consult the new battery instructions to obtain more information on this Do not dispose of batteries...

Page 3: ...3 Checking the power supply source 3 Checks prior to installation 4 Protection against transient interferences 4 Cleaning 4 Mounting Series MPS 5 2 LED Description and Operation 6 Features of SSG Powe...

Page 4: ...element 1 If after unpacking the Series SSG power supply source and making a visual inspection you find that it has been damaged in any way YOU SHOULD NOT carry on with installation but rather you sh...

Page 5: ...nterferences Just like all electronic equipment this system may function irregularly when subject to electrical discharges Although no system is completely immune from electrical discharges a proper E...

Page 6: ...ed on the wall and mark the position of the screw holes making sure that the center one is leveled The following illustration shows the box and the screw holes through the back Do not use the rear box...

Page 7: ...ms 6 FRONT PANEL 2 LED DESCRIPTION AND OPERATION INTERNAL LEDS GENERAL FAULT SERVICE PRIMARY POWER SUPPLY FAULT BATTERY CHARGER FAULT BATTERIES NOT CONNECTED FAULT LOW BATTERY WARNING EARTH SHUNT SYST...

Page 8: ...he primary power supply conditions The two source models are similar they are composed of a power supply module of 45W 65W and 2 x 65W for supply sources SSG1 5 SSG2 5 and SSG5 respectively and an ele...

Page 9: ...ch is indicated after a delay of some 8 minutes in order to prevent failures due to intermittent blackouts Fault Relay Operation Connector J4 FAULT with three terminals Terminal 1 Left C common Termin...

Page 10: ...ative OUTPUT 2 PSO2 Output 2 positive PSO2 Output 2 negative FAULT RELAY FAULT C Fault relay common FAULT NC Contact normally closed FAULT NO Contact normally open MAINS IN MAINS IN Equipment earth MA...

Page 11: ...f a connection fault or else because they are at low discharge level and the control disconnects them for protection It blinks when the batteries are at the last level of discharge before disconnectio...

Page 12: ...nt per output 630mA SSG 1 5 1 A SSG 2 5 2 A SSG 5 Battery charge current 300mA 7 Amp hour 600mA 17 Amp hour Charges batteries to 80 in less than 24 hours and to 100 in less than 48 hours Faulty Relay...

Reviews: