SIMPLICITY PLUS / SIMPLICITY MICRO – ADDITIONAL FEATURES.  

 

Software Version  :PANEL-R6180 (Plus) R5780 (Micro)

 

Approved Document No: GLT.MAN-139

 

 

 

PAGE 5 

Issue 1.00         Authorised: GH      Date: 02/06/2010

 

5 CHANGING THE ALARM RESPONSE - SOUNDERS 

 
By Default, the Simplicity uses a common alarm configuration. IE any alarm sets off all  
sounders. This default operation may not be suitable for every installation.  As alarms from 
Manual Call points often need to be treated differently, the operation of detectors & call 
Points can be configured separately. Enter Configuration Menu 2 & select System Menu  
(option 6) Select option 3 (Alarms). 
NOTE that if ADDRERSSABLE COMMON SOUNDER BASES are used, the SOUNDER 
Response can ONLY be COMMON, as these sounders can not be individually controlled. 
 

5.1 Changing Detector Alarm Response 

 

To change the alarm response of detectors, select option 1. The following screen is  
Shown. Use Prev/Next  buttons to scroll between the options Common and Zonal.  
Press enter to confirm. 
 

5.2 Changing MCP Alarm Response 

 

To change the alarm response of manual call points, select option 2. The following  
screen is shown. Use Prev/Next  buttons to scroll between the options Common and  
Zonal.  Press enter to confirm. 
 

5.3 Zonal Sounder  to Common Sounder Delay 

 

If Zonal sounder operation is selected, in the event of an alarm, the sounders will only  
ring in a certain part of the building (the zone that signalled the alarm). Sometimes there  
is a requirement to start all the other sounders if the alarm continues for a given time.  
On the Simplicity system, we refer to this as the Zonal to Common sounder time. 
 
Select option 3 from the alarm operation menu. This zonal to common sounder time can  
either be disabled (IE alarms stay zonal), or it can be enabled. IE all the sounders will start  
after the programmed time delay.  
 
To alter this delay, go to the EDIT SYSTEM MENU and select option 4 (Timing) 
 
 
 
The panel will bring up the following menu. Select option 1 (Zonal to common) 
 
 
 
The panel will now show the currently selected delay time. This can be set between  
30 seconds and 10 minutes, in 15 second increments, using the previous and next  
buttons. Press enter to confirm the selected time. 
 

5.4 Associated Sounder Base Settings 

 
On previous Simplicity Panels, associated sounder bases have always been common  
acting. There is now an option for them to be zonal. In the Alarm Operation Menu,  
select option 4 (bases). 
 
Use Prev / Next to select common or Zonal operation, then press enter. 
 
 
 
 

  Sounder Operation 
   Detector Alarm 
       Common 
   ENTER to Confirm

 

 

System Menu 
1: Clock  4: Timing 
2: Zones  5: Misc 
3: Alarms 6: Reset

 

Alarm Operation 
1: Det    4: Bases 
2: MCP    5: I/O 
3: Sounder

 

 

  Sounder Operation 
  Manual Call Point 
       Common 
   ENTER to Confirm

 

 

  Sounder Operation 

 Zonal-Common Time 

      Disabled 
   ENTER to Confirm

 

 

System Menu 
1: Clock  4: Timing 
2: Zones  5: Misc 
3: Alarms 6: Reset

 

Alarm Timing 
1: Zonal to Common 
2: Alarm Verify 
     

 

  Zonal-Common Time  
        0:30 

 

   ENTER to Confirm

 

 

Alarm Operation 
1: Det    4: Bases 
2: MCP    5: I/O 
3: Sounder

 

 

Alarm Operation 
1: Det    4: Bases 
2: MCP    5: I/O 
3: Sounder

 

 

  Sounder Operation 
    Sounder Bases 
       Common 
   ENTER to Confirm

 

 

Summary of Contents for SIMPLICITY PLUS

Page 1: ...MPLICITY MICRO ADDITIONAL FEATURES Software Version PANEL R6180 Plus R5780 Micro Approved Document No GLT MAN 139 PAGE 0 Issue 1 00 Authorised GH Date 02 06 2010 ANALOGUE ADDRESSABLE FIRE ALARM PANEL ADDITIONAL FEATURES ...

Page 2: ...Alarm Response 5 5 2 Changing MCP Alarm Response 5 5 3 Zonal Sounder to Common Sounder Delay 5 5 4 Associated Sounder Base Settings 5 6 CHANGING THE ALARM RESPONSE I O UNITS 6 6 1 Types of I O UNIT Operation 6 6 2 Setting Default I O UNIT Operation 6 6 3 Setting Individual I O UNIT Operation 6 7 SETTING THE LCD LANGUAGE 6 8 ALARM VERIFICATION 7 8 1 How Alarm Verification Works 7 8 2 Setting the Al...

Page 3: ...st sees devices A device out of the panel s address range will be reported EG a detector at address 80 on a Simplicity 64 User definable zones Option for zonal or common alarm operation Options for I O operation Alarm Verification User selectable languages Options to reset panel to factory settings On the Simplicity Plus the CPU card is now integrated on the display PCB so is no longer user upgrad...

Page 4: ...ter button to configure the loop The panel will show Configuration in progress for about 9 seconds then it will then return to the system normal screen The loop is now configured 3 Reduced Loop Simplicity Panels For the reduced loop capacity Simplicity panels EG Simplicity Micro or Simplicity Plus 64 it is possible to address a device outside the panels range Previous versions of simplicity panel ...

Page 5: ...ER to save or press CANCEL to keep the existing Address 6 The Zone will now change to the selected boundary with the first device of the next zone changing accordingly Eg just changing zone 1 last device to 10 would result in zone 1 being addresses 1 to 10 Zone 2 being 11 to 32 zone 3 being the default 33 to 48 etc NOTE If the building plans have not been finalised it would be wise to leave a few ...

Page 6: ...equirement to start all the other sounders if the alarm continues for a given time On the Simplicity system we refer to this as the Zonal to Common sounder time Select option 3 from the alarm operation menu This zonal to common sounder time can either be disabled IE alarms stay zonal or it can be enabled IE all the sounders will start after the programmed time delay To alter this delay go to the E...

Page 7: ...2 Setting Default I O UNIT Operation To set the simplicity panels default I O operation enter configuration menu 2 then select config system to bring up the system menu Select Option 3 Alarms to bring up the alarm operation Menu Select option 5 I O This brings up the following screen Press Prev Next to select the default operation then press enter 6 3 Setting Individual I O UNIT Operation To alter...

Page 8: ...alarm 5 If a detector WITHOUT verification setting goes into alarm the panel will go straight into full alarm With this method of operation a cooking alarm in one apartment will alarm locally giving the apartment occupants a chance to clear the smoke before the whole building is evacuated Also as a failsafe if a heat detector alarms or if a second smoke detector on the system goes into alarm the s...

Page 9: ...o their default setting 3 Panel Resets alarm response back to all common resets system timers 4 Devices Clears device information from memory and clears device label device configuration 6 All Performs 2 3 4 in one operation When you select to reset a section the panel will display something like Press enter to confirm or cancel to abort the action The panel will then warn that this action can not...

Page 10: ...sociated sounder Select alarm verification Turn off associated sounder at this address Disable this device Select specific I O Operation for an I O unit 6 Config System System Menu 1 Clock Adjust time date 2 Zones Change zone boundaries 3 Alarms Alarm Operation 1 Det Choose detectors to cause zonal alarm or common alarm for sounders 2 MCP Choose MCP to cause zonal alarm or common alarm for sounder...