background image

SIMPLICITY PLUS INSTALLATION MANUAL

 

 

 

 

Approved Document No: GLT.MAN-107 

 

  

PAGE 31

 

Issue 3.16         Author: NRPJ      Date: 21/09/2017 

13. ALARM VERIFICATION 

The Simplicity now includes an option to use alarm verification. 
It is intended for use in apartments, and similar buildings, where it is desirable that an alarm from one apartment (or 
area) would need to be confirmed before the whole system goes into alarm. 

13.1 HOW ALARM VERIFICATION WORKS 

The verification function works as follows:- 
Any SMOKE detector on the system can be set to verify an alarm. 
If a detector with the verification setting senses smoke, the detector alarm led will turn on. If the detector has an 
associated sounder base, the sounder will turn on with the Alert tone (i.e. pulsed) rather than the Evacuate tone. The 
Simplicity panel’s screen will show “Confirming alarm” and the PRE-ALM LED will start flashing. 
If the detector drops below the alarm level within the programmed verification time (60 seconds to 3 minutes 45 
seconds), the sounder will turn off and the PRE-ALM LED will turn off, but the panel will continue displaying “Confirming 
Alarm” for at least 5 minutes. The buzzer will also continue to operate as long as the “Confirming Alarm” message is 
displayed. 
If the detector stays in alarm by the end of the verification delay, the system will go into full alarm. 
If another detector WITHOUT verification setting or a call point goes into alarm, the panel will go straight into full alarm. 
With this method of operation a “cooking alarm” in one apartment will alarm locally, giving the apartment occupants a 
chance to clear the smoke before the whole building is evacuated. Also, as a “failsafe”, if a heat detector alarms, or if a 
second smoke detector on the system goes into alarm, the system will go into full alarm. 
13.2 SETTING THE ALARM VERIFICATION DELAY 

To set the verification delay, go to Configuration menu 2 and select option 6 System menu. 
From the system menu, select option 4 (timing) 

System Menu 
1: Clock  4: Timing 
2: Zones  5: Misc 
3: Alarms 6: Reset 

 

From the alarm timing screen, select option 2 (Alarm Verify) 
Use Prev & Next to adjust the time, then press enter to confirm 

Alarm Timing 
1: Zonal to Common 
2: Alarm Verify 
 

 

13.3 APPLYING ALARM VERIFICATION DELAY TO A DETECTOR 
To set the verification delay for a detector, go to Configuration menu 2 and select option 5 (Edit 
Device). 

Detector Verify Time 

1:30 

 

ENTER to Confirm 

 

Scroll to the required device, then press V for Verification. The letter V appears in the top right 
hand corner to confirm that this device now has the verification delay. Pressing “V” again will 
toggle the Verification off. 

Optical    

         

V

 

 

Analog:  25  Normal 
Fl 3 Bedroom 303 
Zone:01       Ad:016 

 

 

Summary of Contents for Simplicity Plus 126

Page 1: ...SIMPLICITY PLUS INSTALLATION MANUAL Approved Document No GLT MAN 107 Issue 3 16 Author NRPJ Date 21 09 2017 ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION MANUAL...

Page 2: ...ontrol Module 15 7 1 6 ZAZM MI Conventional Zone Module 16 7 1 7 Xtratone Sounder Sounder Flasher 16 7 1 8 Sandwich Sounder 16 7 1 9 Remote LED Indicator 16 7 1 10 Isolator Base 17 7 2 MAXIMUM LOOP LE...

Page 3: ...DISABLEMENTS DURING A FIRE ALARM CONDITION 36 17 DISABLEMENT 37 17 1 ZONE DISABLEMENT 37 17 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED 37 17 3 DEVICE DISABLEMENT 37 17 4 VIEWING DISABLEMENTS 38 17 4...

Page 4: ...ic Always handle PCBs by their sides and avoid touching the legs of any components Keep the PCBs away from damp dirty areas e g in a small cardboard box 1 2 SAFETY PRECAUTIONS DURING NORMAL OPERATION...

Page 5: ...irements The Simplicity Plus also has the following ancillary functions not required by the Standard Class Change Input to allow remote activation of sounders Serial repeater output RS485 Serial Outpu...

Page 6: ...e individual devices or whole zones Detector LED sounder can be operated from the menu to help identify devices Panel software version can be viewed through menu The 64 could be upgraded to a 126 by c...

Page 7: ...PANEL LOOP ADDRESS LOOP ADDRESS DEVICE LABEL 20 CHARACTERS for device PLUS 20 Characters for the ZONE 20 CHARACTERS PREALARM PRESET 45 PRESET 45 DETECTOR SENSITIVITY PRESET 55 PRESET 55 ZONE ALLOCATI...

Page 8: ...in a step by step manner the procedure for the basic design and installation of the Simplicity Plus Range of Fire Alarm Control Panels It gives detailed instructions on how to use all the features on...

Page 9: ...1 to 96 Zone 7 Addresses 97 to 112 Zone 1 Addresses 1 to 16 First Zone 4 Addresses 49 to 64 Zone 5 Addresses 65 to 80 Zone 1 Addresses 1 to 16 Ground Zone 2 Addresses 17 to 32 Zone 3 Addresses 33 to 4...

Page 10: ...5839 Pt1 2013 Clause 26 are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resisting cable to PH120 classification of EN 50200 Note that all cables should be at least 1...

Page 11: ...all using the three mounting holes provided Check the build condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 roundhead or countersunk woodscrews or simi...

Page 12: ...hould be passed twice through the provided ferrite This is made easier by removing the outer insulation The cable is then connected to the Live Earth and Neutral connections marked on the power supply...

Page 13: ...of Battery 1 to the black battery charger lead Connect the ve of Battery 2 to the red battery charger lead The ve of the first battery is connected to the ve of the second battery using the FUSED lin...

Page 14: ...olator fitted This is to prevent a short circuit fault in one zone affecting another zone Note that some Devices for example a sounder controller circuit may require a separate 24 volt supply to opera...

Page 15: ...t terminal on the call point The following terminals are used for connecting the call point 2 x Negative in terminals note if you only connect to the negative in terminals then the isolator is bypasse...

Page 16: ...d of line resistor value is 20K and the trigger resistor value is 1K 7 1 5 ZASC MI Sounder Control Module The ZASC requires a external 24vdc power supply as shown in the above diagram The EOL for the...

Page 17: ...minals in the back box of the device Please refer to the above diagram 7 1 8 Sandwich Sounder The sandwich sounder has no wiring to connect as it just clips straight on to a standard base It will run...

Page 18: ...using 1 5mm cable can have a maximum loop run of 1250m end to end 7 3 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device 1...

Page 19: ...ON ON OFF ON ON 59 OFF OFF ON OFF OFF OFF ON 102 ON OFF OFF ON ON OFF OFF 17 OFF ON ON ON OFF ON ON 60 ON ON OFF OFF OFF OFF ON 103 OFF OFF OFF ON ON OFF OFF 18 ON OFF ON ON OFF ON ON 61 OFF ON OFF OF...

Page 20: ...it might be possible to speed up the sounder base start stop time See CONFIGURING ASSOCIATED SOUNDERS section 8 3 SANDWICH SOUNDER BASES ADDRESSD MODE The sandwich sounder can be given an address wit...

Page 21: ...take a few seconds There are 2 methods to speed up the stop times of these sounders 1 For ease of functional checking during installation the simplicity panel assumes that every detector found during...

Page 22: ...condition It can be connected to emergency lights local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Extra alarm relays can be achieved by fit...

Page 23: ...NATING THE WIRING Figure 6 Cable connections All cables entering the enclosure should have cable glands which will prevent unwanted openings in the enclosure The Addressable Loop circuits should be co...

Page 24: ...upports up to 4 repeaters Connections See Section 21 for the serial repeater connections 11 2 SERIAL PRINTER CONNECTION The Simplicity has an RS232 Serial output that transmits panel events as they oc...

Page 25: ...nu 2 In this menu there are options to Configure the loops to edit each device and to configure the system options The arrow in the bottom left hand corner shows that pressing PREVIOUS button will ret...

Page 26: ...every detector has a sounder base or if most of the detectors have a sounder base this speed up operation will have little or no effect 1 Press enter NEXT followed by 369 to enter Configuration Menu...

Page 27: ...area The minimum number of addresses per zone is 2 Zone Boundaries Zone 1 001 010 ENTER to Change All 8 zones do not need to be use i e the 126 device version could be configured as 6 zones of 21 dev...

Page 28: ...common or Zonal operation then press enter Sounder Operation Sounder Bases Common ENTER to Confirm 12 9 CHANGING THE ALARM RESPONSE I O UNITS Because a system could have several I O units each reactin...

Page 29: ...o to configuration menu 2 Select Edit Device Scroll to the required Address Press Button I for Input to cycle through the different Triggering Options of I O configuration The different options are Le...

Page 30: ...nguage Bank 2 English Hungarian Serbian Lithuanian Configuration Menu 2 4 Configure Loops 5 Edit Device 6 Config System 12 11 SOFTWARE VERSIONS From Configuration menu 2 Select configure system option...

Page 31: ...l From Configuration menu 2 Select configure system option 6 Then from the Misc Settings menu select option 3 Protocol Press Prev Next to select Standard or Fyreye Mk2 protocol and then press ENTER NO...

Page 32: ...ector stays in alarm by the end of the verification delay the system will go into full alarm If another detector WITHOUT verification setting or a call point goes into alarm the panel will go straight...

Page 33: ...se back to all common resets system timers 4 Devices Clears device information from memory and clears device label device configuration 6 All Performs 2 3 4 in one operation When you select to reset a...

Page 34: ...not to ring any sounders 2 MCP Choose MCP to cause zonal alarm or common alarm for sounders 3 SOUNDER Select if the sounders have a zonal to common time out when triggered zonally 4 Bases Select if a...

Page 35: ...e following messages Optical Changed Analog 25 Fault Fl 3 Bedroom 303 Zone 01 Ad 016 FAULT MEANING Changed The device had been changed with one of a different type since last configuration The message...

Page 36: ...nd the Zone loop and address if appropriate Next Previous buttons will cycle through the list Event 173 25 01 2007 17 21 Device Alarm Zone 01 Lp 1 Ad 013 System The Simplicity also records other non c...

Page 37: ...s in the second zone that went into alarm etc To view the alarms chronologically the event log must be used FIRE First Z01 2 of 2 Last Z02 Kitchen Zone 02 Ad 017 16 2 VIEWING FAULTS DURING A FIRE ALAR...

Page 38: ...and the Zone or Sounder LED will come on steady along with the GENERAL DISABLEMENT LED This section is now disabled NOTE Call points in this zone will also be disabled To keep the call points functio...

Page 39: ...e screen will show Zone Disablement Zone 1 Zone Enabled Disabled Devices 0 If a zone is disabled the screen will show Zone Disablement Zone 1 Zone Disabled Disabled Devices 0 If there are one or more...

Page 40: ...is zone can now be tested with smoke spray The Detector will light its LED until the smoke clears then it will reset The Sounders the fire relay are not operated during test mode Once testing of that...

Page 41: ...doubt contact your supplier If the wiring polarity is correct check that there is no cable break on the loop If there is a break the panel will report the break after 60 seconds or so and inside the p...

Page 42: ...nomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and fault internal buzzer will be constantly active...

Page 43: ...vices wait for the zone fault LED check the addresses in that zone then there is probably a short circuit on the loop look for isolators lit Yellow or flashing The missing devices should give an indic...

Page 44: ...13 2 10 20 Fyreye Addressable Beam Detector 5 50m ZT BEAM SMM B 5 7 9 16 32 Sandwich Sounder Base MKII SSB 0 6 N a 7 5 32 64 Zeta Addressable Maxitone Sounder MKII AMT 0 6 N a 7 0 32 64 Zeta Addressab...

Page 45: ...Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr TSBY 24 Hr IQP 0 105A Quiescent current for panel IQD 80 x...

Page 46: ...LOOP 1 Connect to detector wiring loop 1 4 FIRE RELAY Volt free relay Operates on any alarm 5 FAULT RELAY Volt free relay normally energised Operates on any fault 6 CLASS CHANGE Remote input to opera...

Page 47: ...for the second 24 V output 6 B FUSE Fuse for the second 24V output 7 BATTERY Battery connection 2 x 12V SLA batteries wired in series 8 FACTORY ADJUST Charger adjust pot DO NOT ADJUST 9 THERM Battery...

Page 48: ...SOUNDER ALARM OUTPUTS LOOP POWERED SOUNDERS ONLY AUXILIARY FAULT OUTPUT 1 x FAULT RELAY SELV 1A NORM ENERG AUXILIARY FIRE OUTPUT 1 x FIRE RELAY SELV 1A NUMBER OF LOOPS SIMPLICITY PLUS 64 1 LOOP SIMPL...

Page 49: ...2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings Simplicity Plus SP 64 M SP 126 M SP 252 M Provided options Output to fire al...

Page 50: ...d enclosure designed for 7AH comment in battery calc section refers to Original Plastic version of panel 3 13 29 8 2012 Corrected Max loops Devs to reflect 2 loop version sect 22 2 NOTE Use PDF Printe...

Reviews: