PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 26
Issue: 1.5
Date: 02/04/2014
Fault display & fault-finding
The Premier EVACS 1-16 panel monitor for the following faults:-
Power Supply Fault
Speaker Channel open-circuit wiring fault
Speaker Channel short-circuit wiring fault
Earth Fault
Amplifier Fault
System Fault
The Premier EVACS 1-16 Voice Alarm panel also has a General Fault LED that will light when any fault is present.
Most of these faults will need to be checked by an engineer.
All faults in the Premier EVACS 1-16 are NON-LATCHING. IE they cannot be reset with the reset button. They will
clear automatically when the fault has been fixed.
Fault Finding
Power Supply fault
A power supply fault is indicative of one or more of the following faults: -
Loss of Mains power
Check that 230V AC is present at the mains terminal block
Check mains fuse
Check charger fuse FS1.
Loss of Battery power
Check that 2 X 12V batteries are fitted in series to give 24V backup
Check battery fuse
Check that battery connections are secure.
Check that the batteries are not over 5 years old
Loss of Charger
The Power supply will monitor the charger circuit. In the rare event of a component failure that affects the charger,
the PSU will bring up a fault.
Loss of Battery Capacity
The Power supply will monitor the Battery condition. If it detects a high internal resistance, which usually means a
loss of capacity in the battery, it will bring up a fault.