PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 12
Issue: 1.5
Date: 02/04/2014
Controls
The Premier EVACS 1-16 has the following controls:-
LABEL
USE
TEST
LED and buzzer test
ALARM
Used to initiate manual playback of the Evac / Alarm Message
ALERT
Used to initiate manual playback of the Alert Message
DISABLE
Used to disable one or more of the speaker channels
SILENCE
Used to silence the panels fault buzzer
RESET
Used to reset the system from the voice alarm condition
STOP / START
Used to Manually start playback of a selected message, or to stop an
existing message.
1 - 16
Select buttons for channels 1 to 16
Speaker circuits
The EVACS 1-16 has two 667Ω speaker outputs running at 100v nominal allowing up to 30W RMS output per channel
Wiring the speakers
Te premier EVACS II checks for line integrity by using a 10K End of Line resistor on each speaker circuit, which should
be connected to the last speaker on the circuit. The end-of-line resistor should be rated at 1W or higher
Sounder circuits
The EVACS 1-16 has two sounder outputs that activate alongside the speaker outputs; they are each rated at 500mA
at 28V DC (nominal) and are over-current protected by a self-resetting fuse. The sounder circuits are monitored and
require a 10K End of line resistor rated at 1/8w or higher.