INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 36
18. TEST MODE
18.1 Why use test mode
To aid commissioning and assist routine maintenance check, a silent, non-latching ‘one man test’ facility is
available.
When a detector or manual call point is triggered on any zone in Test, the Device will light it`s LED, When the
smoke has cleared, or the call point has been reset, the LED will turn out.
Should an Alarm occur on a zone that is not programmed to test, the Fire Alarm Panel will go into full alarm. The
Zone test LED will continue to be lit. When the alarm has been reset, test mode will resume
18.2 To programme zone in test mode
NOTE: Only
one zone
can be programmed in test at any one time.
1. Enter the user password 123;
2. Press TEST Button. The screen will prompt for the test code
3. Enter the Test code
2 4 8.
4. The screen will now invite you to select the zone to be tested, as follows:
5. Press TEST FUNCTION SELECT button to select the zone to be
tested.
6. Press CONFIRM to enter test mode for this zone
The General Test and Zone Test LEDs will now be lit.
7. Detectors in this zone can now be tested with smoke spray. The
Detector will light it`s LED until the smoke clears, then it will reset. The
Sounders & the fire relay are not operated during test mode.
8. Once testing of that zone is completed, press TEST FUNCTION SELECT button to move to another Zone or
Press CANCEL to exit test mode.
18.3 To program sounder circuits in test mode
1. Enter Access Code (123)
2. Press General TEST Button, The screen will prompt for the test code.
Enter the code 2 4 8.
3. The screen will now show Test Mode, Zone 1, Normal Operation.
4. Press NEXT button several times to select the Required
SOUNDERS. (External sounder circuit 1, 2, or Line (Zone) sounders
5. Press ENTER test mode for this function. The general test LED
will now be lit.
6. The Sounders will now pulse 8 seconds on, 8 seconds off until
they are taken out of test mode. This allows all the sounders
to be tested for correct operation, and dB output.
7. Once testing of the sounder circuit is completed press CANCEL
exit test mode.
Select Zone to Test
Zone 1
Normal Operation
Enter Access Code
█
Select Zone to Test
Zone 1
Test Active
Zone 1
Select Zone to Test
Zone 1
Normal Operation
Enter Access Code
█
Select Zone to Test
Line Sounders
Test Active
Line Sounders