ADDRESSABLE XTRATONE SOUNDER BEACON - INSTALLATION MANUAL

ADDRESSABLE XTRATONE SOUNDER BEACON

INSTALLATION MANUAL

Connections - First Fix

The loop wiring connects to terminals in 

the back box.

Earth

Not Used

Loop In/Out 

Positive

Loop In/Out 

Negative

Final Fix

• 

Set the device address (see address 

setting)

• 

Fix the BROWN sounder flying lead to 

the POSITIVE terminal

• 

Fix the BLUE sounder flying leads to 

the RIGHT NEGATIVE terminal

• 

Screw the sounder body to the backbox

• 

 Fit the sounder front cover

Flying Leads

Sounder Body

8 Way DIP Switch

Front Cover

Description

The Xtratone addressable sounder beacon 

is a small, high output device, suitable for 

indoor wall mounted applications.

It is available in red or white and has a 

selection of 16 alarm tones, selectable at 

the control panel. 

Termination of field wiring is made to the 

backbox for a clean first fix.

Summary of Contents for MKII-AXTB/R

Page 1: ...dress setting Fix the BROWN sounder flying lead to the POSITIVE terminal Fix the BLUE sounder flying leads to the RIGHT NEGATIVE terminal Screw the sounder body to the backbox Fit the sounder front co...

Page 2: ...ernative Soft Addressing Option Using our hand held MkII programmer Part No 48 004 the sounder can be addressed electronically Step 1 Set all addresses to zero 0000000 Step 2 Connect leads to LOOP IN...

Page 3: ...50 per second 5 BS Fire Alternating 510 610 1Hz 500ms 500ms 6 German fire DIN 33 404 Sweep DIN 1200 to 500 1Hz 7 French fire NFS 32 001 Alternating 554 440 100ms 400ms 8 Dutch fire NEN 2575 Slow whoop...

Page 4: ...sher rating Setting Switch 1 Switch 2 Switch 3 Flash rate Current Relative Flasher intensity 1 OFF OFF OFF 0 5 Hz 43mA 100 2 ON OFF OFF 0 33 Hz 18mA 60 3 OFF ON OFF 0 33 Hz 25mA 85 4 ON ON OFF 0 33 Hz...

Page 5: ...56 105 x 105 x 89 105 x 105 x 56 105 x 105 x 89 Weight with Back Box 200g 210g Minimum sound output 66 3dB Troubleshooting Problem Possible Cause Device Not Seen By Panel Check the device is addresse...

Page 6: ...ON ON 61 OFF ON OFF OFF OFF OFF ON ON 62 ON OFF OFF OFF OFF OFF ON ON 63 OFF OFF OFF OFF OFF OFF ON ON ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 64 ON ON ON ON ON ON OFF ON 65 OFF ON ON ON ON ON OFF ON...

Page 7: ...248 ON ON ON OFF OFF OFF OFF OFF 249 OFF ON ON OFF OFF OFF OFF OFF 250 ON OFF ON OFF OFF OFF OFF OFF 251 252 253 254 255 ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 128 ON ON ON ON ON ON ON OFF 129 OFF ON...

Page 8: ...rocessing site as per the guidelines of the WEEE directive for correct disposal Zeta Alarms Ltd 72 78 Morfa Road Swansea SA1 2EN 0832 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 17 0832 CPR F...