ADDRESSABLE XTRATONE SOUNDER BEACON - INSTALLATION MANUAL

Alarm Tone Selection 

The Xtratone sounder beacon supports alarm tone selection. IE, the installer can decide 

which alarm tone ALL the sounders will use. The alarm tone can be set for the whole 

system via the control panel. One of 16 tones can be chosen for the alarm tone.

No Tone Description

Pattern

Frequency Rate

0*

BS Fire (Default Zeta tone)

Alternating

800 & 970

1Hz (500ms-500ms)

1

BS Fire

Alternating

800 & 970

2Hz (250ms-250ms)

2

BS Fire

Sweep

800 to 970

1Hz (1 per second)

3

BS Fire

Sweep

800 to 970

7Hz (7 per second)

4

BS Fire

Sweep

800 to 970

50Hz (50 per 

second)

5

BS Fire

Alternating

510 & 610

1Hz (500ms-500ms)

6

German fire (DIN 33 404)

Sweep (DIN) 1200 to 500 1Hz

7

French fire (NFS 32-001)

Alternating

554 & 440

100ms-400ms

8*

Dutch fire (NEN 2575)

Slow whoop 500 to 1200 3.5s sweep, 0.5 s 

silence, then repeat

9

PFEER Toxic Gas

Continuous

970

Steady

10

PFEER alert 

Intermittent 970

0.5Hz (1s On/1s Off)

11

Reserved

-

-

-

12

Reserved

-

-

-

13

Reserved

-

-

-

14

Reserved

-

-

-

15

Reserved

-

-

-

* Approved Tones

See Document GLT-290-6-1 for further operational data.

Selecting a Reserved tone will cause the sounder to play tone 0. The default alarm tone 

will be tone 0.

Other Tones 

The Xtratone has 3 tones that can be triggered in normal running:-

•  Alarm Tone – Selectable – see list above.

•  Alert tone – 970Hz intermittent. 0.5s on, 0.5s off

•  Emergency - 970Hz intermittent: 3 x 500ms pulses, 1.5s silence, then repeat

The availability of these tones will depend on the Control panel used.

Summary of Contents for MKII-AXTB/R

Page 1: ...dress setting Fix the BROWN sounder flying lead to the POSITIVE terminal Fix the BLUE sounder flying leads to the RIGHT NEGATIVE terminal Screw the sounder body to the backbox Fit the sounder front co...

Page 2: ...ernative Soft Addressing Option Using our hand held MkII programmer Part No 48 004 the sounder can be addressed electronically Step 1 Set all addresses to zero 0000000 Step 2 Connect leads to LOOP IN...

Page 3: ...50 per second 5 BS Fire Alternating 510 610 1Hz 500ms 500ms 6 German fire DIN 33 404 Sweep DIN 1200 to 500 1Hz 7 French fire NFS 32 001 Alternating 554 440 100ms 400ms 8 Dutch fire NEN 2575 Slow whoop...

Page 4: ...sher rating Setting Switch 1 Switch 2 Switch 3 Flash rate Current Relative Flasher intensity 1 OFF OFF OFF 0 5 Hz 43mA 100 2 ON OFF OFF 0 33 Hz 18mA 60 3 OFF ON OFF 0 33 Hz 25mA 85 4 ON ON OFF 0 33 Hz...

Page 5: ...56 105 x 105 x 89 105 x 105 x 56 105 x 105 x 89 Weight with Back Box 200g 210g Minimum sound output 66 3dB Troubleshooting Problem Possible Cause Device Not Seen By Panel Check the device is addresse...

Page 6: ...ON ON 61 OFF ON OFF OFF OFF OFF ON ON 62 ON OFF OFF OFF OFF OFF ON ON 63 OFF OFF OFF OFF OFF OFF ON ON ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 64 ON ON ON ON ON ON OFF ON 65 OFF ON ON ON ON ON OFF ON...

Page 7: ...248 ON ON ON OFF OFF OFF OFF OFF 249 OFF ON ON OFF OFF OFF OFF OFF 250 ON OFF ON OFF OFF OFF OFF OFF 251 252 253 254 255 ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 128 ON ON ON ON ON ON ON OFF 129 OFF ON...

Page 8: ...rocessing site as per the guidelines of the WEEE directive for correct disposal Zeta Alarms Ltd 72 78 Morfa Road Swansea SA1 2EN 0832 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 17 0832 CPR F...

Reviews: