FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE
Faultfinding
Problem
Possible Cause
No response or missing
Incorrect address setting
Incorrect loop wiring
Fault condition reported
Incorrect input wiring
Capacitor not fitted with active EOL
Detector removed
Incorrect EOL
Incorrectly fitted active EOL
Analogue value unstable
Dual address
Loop data fault, data corruption
Constant Alarm
Incorrect wiring
Incorrect end-of-line resistor fitted
Incompatible control panel software
0905
Zeta Alarms Limited,
72-78 Morfa Road, Swansea SA1 2EN
14
GLT-235-DoP-1
EN54-18: 2005
EN54-17: 2005
Fire detection and fire alarm systems – Input/Output Devices
Fire detection and fire alarm systems – Short Circuit Isolators
Zeta Addressable Zone Monitor Module with Isolator
ZAZM-MI
Intended for use in fire detection and fire alarm systems in and around buildings
Response delay (response time) - PASS
Performance under fire conditions - PASS
Operational reliability - PASS
Durability of operational reliability: temperature resistance - PASS
Durability of operational reliability; vibration resistance - PASS
Durability of operational reliability; humidity resistance - PASS
Durability of operational reliability; corrosion resistance - PASS
Durability of operational reliability; electrical stability - PASS