Page 6

FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE

Alternative Soft Addressing Option

Using our hand held MkII programmer (Part No: 48-004), the unit can be addressed 

electronically.

Step 1:

  Set all addresses to zero 0000000

Step 2:

  Connect leads to LOOP IN+ and LOOP IN- as shown below

Step 3:

  Follow the procedure as described in the handheld programmer manual.

NOTE: When a device is soft addressed as above, the address CANNOT BE CHANGED by 

mechanical setting of the dip-switch. In order to re-enable the dip-switch the unit needs 

to be set electronically back to zero first.

Isolator Function

The Isolator Function can be enabled or disabled according to the wiring method.
B. Enabling the Isolator Function

A. By-passing the Isolator Function

Summary of Contents for Fyreye MKII ZAZM-MI

Page 1: ...must be performed to determine the permissable quantity of ZAZM MI per loop Model No ZAZM MI Fyreye MkII Addressable Zone Monitor Module With Isolator Surface Mounting 1 Mount the backbox as required...

Page 2: ...o 010 Author NRP Jones Date 10 05 2021 Page 2 FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR INSTALLATION GUIDE Wiring Details All wiring terminals will accept solid or stranded cables up t...

Page 3: ...1C Size 150 x 90 x 45 mm Weight 220g For information on the short circuit isolator operation see document GLT 224 6 9 available from your distributor LED Indications Status LED Indication Alarm Illumi...

Page 4: ...FF OFF OFF ON ON 61 OFF ON OFF OFF OFF OFF ON ON 62 ON OFF OFF OFF OFF OFF ON ON 63 OFF OFF OFF OFF OFF OFF ON ON ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 64 ON ON ON ON ON ON OFF ON 65 OFF ON ON ON ON...

Page 5: ...FF OFF OFF 248 ON ON ON OFF OFF OFF OFF OFF 249 OFF ON ON OFF OFF OFF OFF OFF 250 ON OFF ON OFF OFF OFF OFF OFF 251 252 253 254 255 ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 128 ON ON ON ON ON ON ON OFF...

Page 6: ...0000 Step 2 Connect leads to LOOP IN and LOOP IN as shown below Step 3 Follow the procedure as described in the handheld programmer manual NOTE When a device is soft addressed as above the address CAN...

Page 7: ...rmed 0 RESET 0 Normal 1 Reset on 0 RESET 0 Normal 1 Reset on Input Condition and Status Status Safe Area Circuit Analogue LED State Short circuit fault 150 8 Indeterminate 150 200 8 or 192 Alarm Alarm...

Page 8: ...05 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 14 GLT 235 DoP 1 EN54 18 2005 EN54 17 2005 Fire detection and fire alarm systems Input Output Devices Fire detection and fire alarm systems Shor...

Reviews: