REFRIGERATION
LOW TEMP (CONT.)
Figure 24: Refrigeration Line Sizing - Ice Cream
R-404 Line Sizing Tables for Zero Zone VZ Ice Cream Freezer (-16°F Evaporator Temperature)
Liquid Line Sizing - Electric Defrost*
Up to 50 equivalent feet
Up to 100 equivalent feet
Up to 150 equivalent feet
Up to 200 equivalent feet
90°F Liquid, 2°F Pressure Drop
∆
90°F Liquid, 2°F Pressure Drop
∆
90°F Liquid, 2°F Pressure Drop
∆
90°F Liquid, 2°F Pressure Drop
∆
From
To
Liquid Line
From
To
Liquid Line
From
To
Liquid Line
From
To
Liquid Line
0
7,090
1/4
+
0
4,830
1/4
+
0
3,850
1/4
+
0
3,270
1/4
+
7,100 14,600
5/16
+
4,840
9,930
5/16
+
3,860
7,930
5/16
+
3,280
6,750
5/16
+
14,610 26,500
3/8
9,940 18,200
3/8
7,940 14,500
3/8
6,760 12,400
3/8
26,510 62,800
1/2
18,210 43,100
1/2
14,510 34,500
1/2
12,410 29,400
1/2
62,810 117,000
5/8
43,110 80,900
5/8
34,510 64,800
5/8
29,410 55,400
5/8
*
For hot gas defrost, use a liquid line one size larger than shown.
64,810 108,000
7/8
†
55,410 92,100
7/8
†
∆
For 1°F pressure drop, multiply rated Btuh by 1.45 before using the Liquid Line Sizing Table.
+
Larger liquid line size may be used (such as 3/8), if preferred.
†
3/4 liquid line may be used to reduce cost.
For rated Btuh:
For rated Btuh:
For rated Btuh:
For rated Btuh:
40°F
50°F
60°F
70°F
80°F
90°F
100°F
120°F
0.95
0.94
0.94
0.95
0.97
1.00
1.05
1.23
Liquid Correction Factors for Liquid Line Sizing Table - Use Maximum Liquid Temperature
For maximum liquid temperatures other than 90°F, multiply rated Btuh by liquid correction factor before using the Liquid Line Sizing Table
Maximum Liquid Temperature:
Liquid Correction Factor:
110°F
1.12
Suction Horizontal Line Sizing
Up to 50 equivalent feet
Up to 100 equivalent feet
Up to 150 equivalent feet
Up to 200 equivalent feet
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
From
To
Horizontal
From
To
Horizontal
From
To
Horizontal
From
To
Horizontal
0
1,420
3/8
++
0
970
3/8
++
0
770
3/8
++
0
660
3/8
++
1,430
3,360
1/2
++
980
2,290
1/2
++
780
1,840
1/2
++
670
1,560
1/2
++
3,370
6,300
5/8
++
2,300
4,320
5/8
++
1,850
3,450
5/8
++
1,570
2,950
5/8
++
6,310 10,500
7/8
†
4,330
7,180
7/8
†
3,460
5,750
7/8
†
2,960
4,910
7/8
†
10,510 16,600
7/8
7,190 11,400
7/8
5,760
9,120
7/8
4,920
7,790
7/8
16,610 33,600
1-1/8
11,410 23,100
1-1/8
9,130 18,600
1-1/8
7,800 15,900
1-1/8
33,610 58,400
1-3/8
23,110 40,300
1-3/8
18,610 32,400
1-3/8
15,910 27,700
1-3/8
58,410 92,300
1-5/8
40,310 63,700
1-5/8
32,410 51,200
1-5/8
27,710 43,800
1-5/8
63,710 132,000
2-1/8
51,210 107,000
2-1/8
43,810 91,000
2-1/8
‡
For 1°F pressure drop, multiply rated BTU by 1.44 before using the Suction Horizontal Line Sizing Table.
++
Larger suction horizontal line size may be used, if preferred.
†
3/4 horizontal suction line may be used to reduce cost.
For rated Btuh:
For rated Btuh:
For rated Btuh:
For rated Btuh:
40°F
50°F
60°F
70°F
80°F
90°F
100°F
120°F
0.72
0.76
0.80
0.86
0.92
1.00
1.10
1.38
Liquid Correction Factors for Suction Horizontal Line Sizing Table - Use Maximum Liquid Temperature
For maximum liquid temperatures other than 90°F, multiply rated Btuh by liquid correction factor before using the Suction Horizontal Line Sizing Table
Maximum Liquid Temperature:
Liquid Correction Factor:
110°F
1.22
Suction Vertical Riser Sizing
Maximum Allowable Riser Size For Adequate Oil Return*
70°F Minimum Liquid Temperature, using 0.35 PSI Per 100 Feet (per 2006 ASHRAE Handbook - Refrigeration).
For rated Btuh:
From
To
Vertical
1,210
2,280
1/2
2,290
3,810
5/8
3,820
6,050
5/8
†
6,060 12,400
7/8
12,410 21,600
1-1/8
21,610 34,300
1-3/8
34,310 71,300
1-5/8
71,310 127,000
2-1/8
*
If horizontal line size is smaller than specified vertical riser size, the smaller size may be used for both.
†
3/4 suction riser may be used to reduce pressure drop.
It may be necessary to make adjustments to compensate for
special situations which cause the actual Btuh to differ from
the rated Btuh of the cases.
All liquid line and suction line sizes are inches, refrigeration O.D.
Subject to change without notice.
Liquid Correction Factors for Suction Vertical Riser Sizing Table - Use Minimum Liquid Temperature
Multiply rated Btuh by liquid correction factor before using the Suction Vertical Riser Sizing Table
40°F
50°F
60°F
70°F
80°F
90°F
100°F
0.83
0.88
0.94
1.00
1.08
1.17
1.28
CCR, 3/29/07
Minimum Liquid Temperature:
Liquid Correction Factor:
SP-0612-02, Rev B
Refrigeration - Low Temp • 27
Summary of Contents for 3RMCC30WA
Page 2: ......
Page 4: ......
Page 36: ...ELECTRICAL LOW TEMP Figure 26 Electric Defrost 30 24 Wiring 32 Electrical Low Temp...
Page 37: ...ELECTRICAL LOW TEMP CONT Figure 27 Hot Gas Wiring Electrical Low Temp 33...
Page 38: ...ELECTRICAL LOW TEMP CONT Figure 28 Single Point Wiring 34 Electrical Low Temp...
Page 39: ...ELECTRICAL LOW TEMP CONT Figure 29 Master Satellite Wiring Electrical Low Temp 35...
Page 40: ...ELECTRICAL MEDIUM TEMP Figure 30 RVCC30 and RMCC24 Wiring Diagram 36 Electrical Medium Temp...
Page 41: ...ELECTRICAL MEDIUM TEMP CONT Figure 31 Single Point Wiring Electrical Medium Temp 37...
Page 42: ...ELECTRICAL MEDIUM TEMP CONT Figure 32 Master Satellite Wiring 38 Electrical Medium Temp...