TROUBLESHOOTING PROCEDURES FOR MONSOON I

Issue

Cause

What to do

After installation, 
the unit doesn’t 
work.

1.  The power source is not turned ON.

1.  Make sure the circuit breaker and the unit’s 

power is ON.

2.  The power line and the cable locking connector 

is not connecting properly.

2.  Check the power connection with the unit is 

connected properly.

3.  The switch board and control board wires are 

disconnected.

3.  Make sure the wires between the switch board 

and control board are connected properly.

4.  The wires on control board are loose.

4.  Make sure the wires on the control board are 

connected properly.

5.  The switch board or control board is defective.

5.  Change the switch board or control board.

Light works, but 
blower is not 
turning.

1.  The blower wire is not connected. 

1.  Make sure the blower wire is plugged into the 

molex connector. 

2.  The thermally protected system detects if the 

blower is too hot to operate and shuts the blower 
down.

2.  The blower will function properly after the 

thermally protected system cool down.

3.  Damaged capacitor.

3.  Change the capacitor.

4.   Blower molex plug pin is not making contact.

4.   Disconnect the blower molex plug, check pins 

inside plug to see if pin is pushed inside the 
plug too far. Reseat pin if needed.

5.  The blower is defective, possibly seized. 

5.  Change the blower. 

The unit is 
vibrating.

1.  The blower is not secure in place.

1.  Tighten the blower in place.

2.  The liner is not secured in place. 

2.  Check the installation of the liner.

3.  Damaged blower wheel.

3.  Change the blower.

The unit is 
whistling.

$¿OWHULVQRWLQWKHFRUUHFWSRVLWLRQ

$GMXVWWKH¿OWHUVXQWLOWKHZKLVWOLQJVWRSV

2.   The duct pipe connections are not sealed or 

connected properly.

2.   Check the duct pipe connections to be sure all 

connections are sealed properly.

The blower is 
working, but the 
lights are not.

1.  The light bulb is loose.

1.  Tighten the bulb and make sure it’s secure.

2.  Defective halogen bulb.

2.  Change the halogen bulb.

3.  The light bulb plug is disconnected.

3.  Connect the light bulb plug.

The hood is 
not venting out 
properly.

1.  The hood might be hanging too high from the 

cook top.

1.  Adjust the distance between the cook top and 

the bottom of the hood within 26” and 36” 
range.

2.  Wind from an opened window or opened 

doors in the surrounding area are affecting the 
ventilation of the hood.

2.  Close all the windows and doors to eliminate 

RXWVLGHZLQGÀRZ

3.  Blockage in the duct opening or duct work.

3.  Remove all the blocking from the duct work or 

duct opening.

4.  The direction of duct opening is against the wind.

4.  Adjust the duct opening direction.

5.  Using the wrong size of ducting.

5.  Change the ducting to correct size.

Filter is vibrating.

1.  Filter is loose.

 $GMXVWRUFKDQJHWKH¿OWHU

 6SULQJFOLSLVEURNHQRQWKH¿OWHU

2.  Change the spring clip.

RF Remote 
control does not 
work

1.  Battery is dead.

1.  Replace battery with type A23 12v.

2.  Poor communication with the liner.

2.  Remote control must be within 15 ft of liner.

3.  RF remote lost communication with the liner.

3.  Reset liner and remote by switching power 

off at the circuit breaker for 5 minutes. Place 
remote on counter top near the liner and 
switch the circuit breaker back on.

T

roubleshooting

Summary of Contents for Monsoon I AK9228AS

Page 1: ...de www zephyronline com Model number Serial Number Date of Purchase Sales Dealer DEC15 0501 2015 Zephyr Ventilation LLC Monsoon I AK9228AS AK9234AS AK9240AS AK9246AS READ AND SAVE THESE INSTRUCTIONS A...

Page 2: ...www zephyronline com...

Page 3: ...binet Preparation Installation 10 Vertical Ducting Preparation 11 Horizontal Ducting Preparation 12 14 FEATURES CONTROLS Touch Controls 15 16 RF Remote Control 17 MAINTENANCE Cleaning and Installing F...

Page 4: ...are and utensils appropriate for the type of and amount of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE OBSERVE THE FOLLOWING D 6027 5 0 6 ZLWK...

Page 5: ...ational Fire Protection Association Batterymarch Park Quincy Massachusetts 02269 CSA International 8501 East Pleasant Valley Road Cleveland Ohio 44131 5575 This appliance requires a 120V 60Hz electric...

Page 6: ...lar cover plate 1 Hardware package HARDWARE PACKAGE CONTENTS PARTS NOT SUPPLIED Ducting conduit and all installation tools Cable connector if required by local codes Light Bulb Removal Suction Cup 1 M...

Page 7: ...0 Round roof cap 30 Ft x Ft Subtotal column 2 Subtotal column 1 Total ductwork Maximum Duct Length For satisfactory air movement the total duct length should not exceed 100 equivalent feet 6 roundto 3...

Page 8: ...t should be no higher than 36 It is important to install the hood at the proper mounting height Hoods mounted too low could UHVXOW LQ KHDW GDPDJH DQG UH KD DUG ZKLOH hoods mounted too high will be har...

Page 9: ...d to the outside Use single wall rigid metal ductwork only DVWHQ DOO FRQQHFWLRQV ZLWK VKHHW PHWDO VFUHZV DQG WDSH DOO MRLQWV ZLWK FHUWL HG 6LOYHU 7DSH RU XFW 7DSH Some Ducting Options Installation Duc...

Page 10: ...0 3 8 46 3 8 12 12 28 14 1 4 34 17 1 4 28 34 5 5 8 1 1 2 C L 28 34 7 3 4 3 10 3 4 22 3 8 28 3 8 34 3 8 40 3 8 19 1 4 28 9 1 4 34 12 1 4 2 9 7 8 C L 3 1 4 elec k o 5 1 2 7 3 4 40 46 5 7 8 40 20 1 4 46...

Page 11: ...ing local codes and ordinances Electrical Supply This appliance requires a 120V 60Hz electrical supply and connected to an individual properly grounded branch circuit protected by a 15 or 20 ampere ci...

Page 12: ...the surface you are securing the liner to is capable of holding the weight of AK92 Failure to do so may cause personal injury or damage to cooking surface or counter 5 Finalize installation of electri...

Page 13: ...E UHPRYLQJ VFUHZV IURP EHKLQG HDFK panel Installation Vertical Ducting Preparation 1 2 1 1 2 Locking Tabs Bottom Panel Screws 2 1 4 Remove bottom panel by 1 5HPRYLQJ screws from left and right sides o...

Page 14: ...HPRYLQJ VFUHZV IURP behind each panel 1 2 1 1 2 Locking Tabs Bottom Panel Screws 2 1 4 Remove bottom panel by 1 5HPRYLQJ screws from left and right sides of bottom panel 2 Pulling bottom panel toward...

Page 15: ...cover plate tabs are on top of the cover plate as shown From inside the liner secure plate to WRS RI OLQHU ZLWK VFUHZV A A B C C B 8 Remove knock outs A and B for rectangular ducting Remove knock out...

Page 16: ...XVLQJ FHUWL HG aluminum duct tape Plug in blower molex plug Horizontal ducting preparation is now complete Refer to Page 10 Step 5 to complete installation 10 Rectangular Ducting From inside the liner...

Page 17: ...crease and to increase speed levels The display indicates levels selected ACT Enabled Speed Selections When ACT is enabled the number of blower speeds will be reduced as follows 390 CFM Maximum 3 spee...

Page 18: ...eset the filter clean reminder timer after filters are cleaned and re installed With hood off press and hold for approximately 5 seconds until on display disappears The filter clean reminder function...

Page 19: ...orage The remote may be placed on any magnetic surface such as a refrigerator or the Zephyr remote holder FIG 4 The remote holder can be inserted into a standard electrical outlet for easy storage Not...

Page 20: ...ntrols LOWHUV PD EH SODFHG LQ GLVKZDVKHU DW ORZ KHDW RU VRDNHG LQ KRW VRDS ZDWHU U OWHUV DQG UH LQVWDOO EHIRUH using hood QVWDOOLQJ WKH DI H LOWHUV 3ODFH OWHU LQWR WRS JURRYH RI WKH OLQHU DV VKRZQ DQG...

Page 21: ...y turning bulb counter clockwise Note Bulb does not unscrew it turns 60 degrees stops and falls out I EXOEV DUH GLI FXOW WR WXUQ GXH WR SURORQJHG XVH UPO DWWDFK WKH JODVV VXFWLRQ FXS SURYLGHG WR WKH E...

Page 22: ...er 3 Damaged blower wheel 3 Change the blower The unit is whistling OWHU LV QRW LQ WKH FRUUHFW SRVLWLRQ GMXVW WKH OWHUV XQWLO WKH ZKLVWOLQJ VWRSV 2 The duct pipe connections are not sealed or connecte...

Page 23: ...imum blower speed WR RQH RI WZR PRVW FRPPRQO VSHFL HG 0 OHYHOV RU 0 7KH XVDJH RI 7 PD QRW EH necessary for your installation Please check your local codes for CFM restrictions By default the maximum b...

Page 24: ...ssure inAq Blower Fan Curve 600 CFM Model AK92 Monsoon I AC Input 120V 60Hz Outlet Diameter 8in 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450...

Page 25: ...23 Fan Curve Wiring Diagrams...

Page 26: ...24 www zephyronline com Fan Curve Wiring Diagrams...

Page 27: ...acement Parts LJKW XOE 05 8 HDFK DI H LOWHU DUJH HDFK DI H LOWHU 6PDOO HDFK RF Remote Control 14000005 To order parts visit us online at http store zephyronline com or call us at 1 888 880 8368 List o...

Page 28: ...ts After the first year from the date of your original purchase you are also responsible for all labor costs associated with this warranty Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE A...

Page 29: ...27...

Page 30: ...our new range hood at www zephyronline com registration Zephyr Ventilation 2277 Harbor Bay Pkwy Alameda CA 94502 1 888 880 8368 Prompt registration helps in more ways than one IT S IMPORTANT Ensures w...

Page 31: ...tallation www zephyronline com Num ro de mod le Num ro de s rie Date d achat D taillant DEC15 0501 2015 Zephyr Ventilation LLC Monsoon I AK9228AS AK9234AS AK9240AS AK9246AS LISEZ ET CONSERVEZ CES INST...

Page 32: ...www zephyronline com...

Page 33: ...tion et installation des armoires 10 Pr paration pour conduit vertical 11 Pr paration pour conduit horizontal 12 14 COMMANDES RPPDQGHV j HI HXUHPHQW 15 16 Commande distance RF 17 ENTRETIEN QVWDOODWLRQ...

Page 34: ...as la hotte sans surveillance lorsque vous cuisinez h Utilisez toujours une batterie de cuisine et des ustensiles convenant au type et la quantit de nourriture que vous pr parez AVERTISSEMENT POUR R D...

Page 35: ...FKHPLQHPHQW GX O HVW DGpTXDW N effectuez pas la mise la terre un tuyau de gaz HPDQGH j XQ pOHFWULFLHQ TXDOL p VL YRXV Q rWHV SDV FHUWDLQ TXH OD KRWWH D pWp PLVH j OD WHUUH DGpTXDWHPHQW N introduisez...

Page 36: ...c registre 1 Adaptateur circulaire de 10 avec registre 1 Adaptateur rectangulaire de 3 1 4 x 10 avec registre 1 Trousse de quincaillerie 2 Supports de montage pour ventilateur avec conduit horizontal...

Page 37: ...utilis rect droit circ droit rect coude 90 rect coude 45 rect coude plat 90 circ coude 90 coude 45 Sous total colonne 1 Longueur maximale du conduit d a ration Pour un mouvement d air convenable la l...

Page 38: ...evrait pas outrepasser 36 Il est important d installer la hotte la hauteur de montage ad quate Les hottes install es trop basses pourraient tre endommag es par la chaleur en plus de pr senter des risq...

Page 39: ...pour cloison simple Fixez toutes les pi ces du conduit avec des vis t le et isolez tous les joints avec du ruban adh sif en toile ou GX UXEDQ Up HFWHXU FHUWL p Quelques options pour le conduit d a rat...

Page 40: ...3 8 12 12 28 14 1 4 34 17 1 4 28 34 5 5 8 1 1 2 L C 28 34 7 3 4 3 10 3 4 22 3 8 28 3 8 34 3 8 40 3 8 19 1 4 28 9 1 4 34 12 1 4 2 9 7 8 C L 3 1 4 5 1 2 7 3 4 40 46 5 7 8 40 20 1 4 46 23 1 4 40 15 1 4 4...

Page 41: ...en vigueur Alimentation lectrique Cet appareil requiert une alimentation lectrique de 120V 60 Hz Il doit tre connect un circuit terminal individuel d ment mis la terre prot g par un disjoncteur de ci...

Page 42: ...TXRL XQH personne pourrait se blesser ou la surface de cuisson ou le comptoir pourraient tre endommag s 5 Terminez l installation des composantes lectriques et du conduit 6FHOOH OH FRQGXLW DYHF GX UXE...

Page 43: ...r vers l avant du bo tier pour le lib rer des languettes de verrouillage 6 La pr paration pour l installation verticale du conduit est termin e Retournez l tape 4 de la page 10 pour terminer l install...

Page 44: ...s languettes de verrouillage 6 Enlevez le ventilateur du bo tier en retirant les 4 vis 3 16 x 3 8 de la partie sup rieure du bo tier Gardez les vis de c t pour une utilisation ult rieure 5 D branchez...

Page 45: ...dessus de la plaque comme illustr Fixez la plaque sur le dessus du bo tier partir de l int rieur l aide des 2 vis 3 16 x 3 8 A A B C C B 8 Enlevez les entr es d fon ables A et B pour installer un cond...

Page 46: ...d fon able avec du ruban conduit en aluminium Branchez le connecteur Molex La pr paration pour l installation verticale du conduit est termin e Retournez l tape 5 de la page 10 pour terminer l install...

Page 47: ...appuyant sur pour diminuer la vitesse et sur pour l augmenter L afficheur indique la vitesse choisie Choix de vitesse avec TCDA activ e Lorsque la TCDA est activ e le nombre de vitesses du ventilateur...

Page 48: ...eur de nettoyage des filtres avec la hotte hors tension Lorsque la hotte est teinte appuyez environ 5 secondes sur la touche jusqu ce que l ic ne disparaisse La fonction de rappel de nettoyage des fil...

Page 49: ...o lectrique est munie d un aimant pour un entreposage facile La commande peut tre mise sur n importe quelle surface magn tique comme un r frig rateur ou le support commande Zephyr FIG 4 Le support com...

Page 50: ...RX OHV IDLUH WUHPSHU GDQV GH O HDX FKDXGH VDYRQQHXVH 6pFKH OHV OWUHV HW UpLQVWDOOH OHV DYDQW G XWLOLVHU OD KRWWH QVWDOODWLRQ GHV OWUHV Gp HFWHXUV 3ODFH OH OWUH YLV j YLV GH O HQWDLOOH VXSpULHXUH FRPP...

Page 51: ...ns contraire des aiguilles d une montre Note les ampoules ne se d vissent pas apr s une rotation de 60 degr s elles s arr tent et tombent de la douille RUVTX LO HVW GLI FLOH GH UHWLUHU OHV DPSRXOHV DS...

Page 52: ...RQ GH OD KRWWH 3 L3 La roue du ventilateur est endommag e 3 Remplacez le ventilateur L appareil met XQ VLI HPHQW XQ GHV OWUHV HVW PDO SODFp MXVWH OHV OWUHV MXVTX j FH TXH OH VLI HPHQW FHVVH 2 Les join...

Page 53: ...iveaux de pi3 min les plus fr quemment utilis s 390 pi3 min ou 290 pi3 min Il est possible que l utilisation de OD 7 QH VRLW SDV UHTXLVH SRXU YRWUH LQVWDOODWLRQ 9HXLOOH YpUL HU OHV FRGHV HQ YLJXHXU GD...

Page 54: ...2 6 2 7 2 8 Pression en TQ Courbe de rendement du ventilateur Mod le AK92 Monsoon I Entr e en CA 120V 60Hz Diam tre du conduit de sortie 8 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 25 50 75 100 125 150 175...

Page 55: ...UNE ORANGE ORANGE GRIS BRUN BLEU BLANC BLANC BLANC NOIR NOIR BLANC CORPS VERT NOIR BLANC 0 90 1 00 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 90 2 00 2 10 2 20 2 30 2 40 2 50 2 60 2 70 2 80 Pression en...

Page 56: ...NE JAUNE JAUNE ORANGE ORANGE GRIS BRUN BLEU BLANC BLANC BLANC NOIR NOIR BLANC BLANC NOIR VERT CORPS 0 90 1 00 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 90 2 00 2 10 2 20 2 30 2 40 2 50 2 60 2 70 2 80...

Page 57: ...Z0B 0023 LOWUH Gp HFWHXU SRXU JUDQG FKDTXH LOWUH Gp HFWHXU SRXU SHWLW FKDTXH Commande distance RF 14000005 3RXU FRPPDQGHU GHV SLqFHV YLVLWH QRXV HQ OLJQH DX ZZZ HSK URQOLQH FRP RX FRPPXQLTXH DYHF QRX...

Page 58: ...stall Un an apr s la date d achat originale du Produit vous tes galement responsable de tous les frais de main d uvre associ s la pr sente garantie Restrictions de la garantie NOTRE OBLIGATION DE R PA...

Page 59: ...27...

Page 60: ...ration Zephyr Ventilation 2277 Harbor Bay Pkwy Alameda CA 94502 1 888 880 8368 Cet enregistrement rapide est utile bien des gards C EST IMPORTANT Il assure la couverture de votre garantie si vous avez...

Reviews: