SIM-CB6 User Manual 

 

Tél : +1 (514) 333-3488 

www.zensol.com

 

 

3

 

 

1.

 

Power the simulator with 120V AC 60 Hz. 

 
2.

 

Connect the actuator extension cable between the three pin connector in the center of the front 
panel (fig 1) and the connector at the end of the actuator. 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 
 

 

Fig. 1 

Fig. 1a 

 

 
 
 
 
 
 
 
 
 
 
 
 

Actuator connector. 

Summary of Contents for CBA-32P

Page 1: ...ZENSOLAUTOMATION INC COMPUTERIZED TEST EQUIPMENT ZENSOL CIRCUIT BREAKER PERFORMANCE ANALYZER CBA 32P CBA 32D Micro CBA MANUAL 11W E SIM CB6 User Manual Version 3 May 3rd 2010...

Page 2: ...SIM CB6 User Manual T l 1 514 333 3488 www zensol com 2...

Page 3: ...zensol com 3 1 Power the simulator with 120V AC 60 Hz 2 Connect the actuator extension cable between the three pin connector in the center of the front panel fig 1 and the connector at the end of the...

Page 4: ...User Manual T l 1 514 333 3488 www zensol com 4 3 Connect the simulated breaker contacts to the timing device For simulated SF6 or air blast breakers use terminals A1 A2 B1 B2 C1 C2 as shown in fig 2...

Page 5: ...The rotary switch allows the activation or deactivation of contact resistance The resistive states of the closing and opening contacts are independent which makes for great flexibility in configuring...

Page 6: ...B6 User Manual T l 1 514 333 3488 www zensol com 6 Configuration example using closing and opening resistors fig 5 and 6 Fig 5 Fig 6 Configuration example without closing resistors fig 7 and 8 Fig 7 F...

Page 7: ...ser Manual T l 1 514 333 3488 www zensol com 7 5 Connect the close and open coils as well as the 24 VDC power supply actually around 28 VDC to the timing device Fig 9 Command cable connections on the...

Page 8: ...1 10 V Pin 3 Ground 6 Connect the output of the TLH 225 transducer to the displacement input of the timing device The three wires function exactly like a three terminal potentiometer Fig 10 Fig 11 Fig...

Page 9: ...l T l 1 514 333 3488 www zensol com 9 7 Manual close and open tests To close press the Close button fig 13 The actuator produces a physical displacement and the contact state indicator becomes red fig...

Page 10: ...SIM CB6 User Manual T l 1 514 333 3488 www zensol com 10 To open press the Open button fig 15 The actuator produces a physical displacement and the contact state indicator becomes green Fig 15...

Page 11: ...www zensol com 11 Note 1 The simulator s front panel fuse is a 3 amp fuse that protects the command logic fig 16 Fig 16 Note 2 The rear panel fuse is a 20 amp fuse that protects the magnetic driver co...