Flat Display v2
Capacitive switch with display and humidity sensor
ZVIFDV2
U
S
E
R
M
A
N
L
Application Programme Version:
[2.5]
User Manual Version: [2.5]_a
www.zennio.com
Page 1: ...Flat Display v2 Capacitive switch with display and humidity sensor ZVIFDV2 USER MANUAL Application Programme Version 2 5 User Manual Version 2 5 _a www zennio com...
Page 2: ...onfiguration 7 General 7 2 1 1 Configuration 7 2 1 2 Advanced Configuration 19 Buttons 25 Display 25 2 3 1 Configuration 25 2 3 2 Disabled 30 2 3 3 Single 30 2 3 4 Double 42 2 3 5 Setpoint 43 2 3 6 Fa...
Page 3: ...buttons is complemented by the built in analogue digital inputs the internal temperature sensor the humidity sensor and the thermostat function as well as an elegant and fully customisable design of...
Page 4: ...nction Up to 5 switchable languages for the displayed texts Two analogue digital inputs for motion detectors temperature probes additional switches etc Thermostat function Built in temperature sensor...
Page 5: ...ntrary if this button is held while plugging the device into the KNX bus the device will enter the Safe Mode In such case the programming LED will then blink in red For detailed information about the...
Page 6: ...ait for about 2 minutes without performing any action to make it possible a proper calibration of Proximity sensor Luminosity sensor Button presses For a correct calibration of the proximity and brigh...
Page 7: ...cess begins by entering the Parameters tab of the device GENERAL To allow the device to perform the desired functions several options must be parameterized either related to its general behaviour scre...
Page 8: ...e it evident that the Display tab is always enabled in the tab tree on the left See section 2 3 for details Inputs disabled enabled enables or disables the Inputs tab in the tree on the left depending...
Page 9: ...wo new communication objects Heartbeat Device Recovery which will be sent to the KNX bus with values 0 and 1 respectively whenever the device begins operation for example after a bus power failure It...
Page 10: ...enabled enables or disables the Touch locking tab in the tree on the left See section 2 1 1 5 for details Proximity Sensor disabled enabled enables the proximity sensor This functionality permits waki...
Page 11: ...bus whenever it is necessary e g when the user touches a button that has been configured to send scene commands General Activity 1 bit object to force activity or inactivity state in the device See P...
Page 12: ...ive 1 bit objects one for each language If this is enabled when a 1 is received through any of this the corresponding language is activated in the device A 1 byte scene object The expected values in t...
Page 13: ...uage is enabled by default While Translations stays enabled the following objects are visible General Translations Select language 1 byte General Translations Main language 1 bit General Translations...
Page 14: ...uration of the related parameters 2 1 1 4 SCREENSAVER The screensaver is a special page that will only be shown after a period of inactivity configurable by parameter Setting the screensaver to only s...
Page 15: ...e device can receive the values from the bus 2 1 1 5 TOUCH LOCKING The touch panel of Flat Display v2 can be optionally locked and unlocked anytime by writing a configurable one bit value to a specifi...
Page 16: ...es the touch locking and unlocking when receiving the configured scene value through the object General Scene receive Lock Scene Number 0 Disabled 0 1 64 scene number that locks the touch Unlock Scene...
Page 17: ...Sending Confirmation a slightly longer and sharper beep than the previous one It indicates the sending of an object to the bus as a result of a press Alarm sharp and longer beep than the previous one...
Page 18: ...bled makes it possible to disable resume the button beeping function in runtime by writing to a specific object General Sounds Disabling Button Sound Button Sound After ETS Download enabled disabled s...
Page 19: ...the indicated object 2 1 2 ADVANCED CONFIGURATION Tab for the parameterisation of some advanced functions is shown in ETS if enabled from the Configuration tab These functions are explained next ETS...
Page 20: ...ming Celsius C Fahrenheit F sets the scale in use after download Figure 9 Temperature Scale After Programming 2 1 2 1 CLEANING FUNCTION This feature is very similar to the touch locking that is it loc...
Page 21: ...ions is selected a new parameter shows up Length of the Warning 1 5 65535 s 1 65535 min h sets the ahead time to start the notification prior to the end of the cleaning function The General Cleaning F...
Page 22: ...ssage by sending the value 1 or to end it by sending the value 0 Figure 11 Advanced Welcome Greeting This screen contains the following parameters Line X Fixed Received from text Object sets whether t...
Page 23: ...at in normal operation may be executed will not be if the welcome back object is sent to the bus Thus if the user presses a button and this causes that the welcome back object is sent the normal actio...
Page 24: ...tion objects is found to have the value 0 Do not send unless at least one of the additional conditions is 1 the welcome back object will only be sent if at least one of the condition objects is found...
Page 25: ...cons or alphanumeric characters texts Please refer to the specific document Icons in Flat Display v2 available at the Zennio homepage www zennio com to see the list of available icons Three different...
Page 26: ...screen and can be configured as a double box Zone B setpoint box is displayed centred on the screen and larger than the other boxes Zone C occupies the right side of the screen and can be configured...
Page 27: ...t indicator and Progressive the icon is progressively drawn from top to bottom The boxes in the screen can be assigned different functions as described next ETS PARAMETERISATION An independent tab for...
Page 28: ...zones when the selected page style is Normal Page Double two small boxes Selecting this option brings the checkboxes Box X1 and Box X2 where X depends on the display zone which turn each of the two z...
Page 29: ...defines the representation of the indicators on the display In case of selecting Every indicator is configured separately there will be a specific parameter for every box to select the desired indica...
Page 30: ...Indicator representation Text text that appears in the display when the alarm is activated Touch Locking sets which push button or pair of push button you wish to lock when the alarm is triggered Ind...
Page 31: ...alue of an object This indicator is totally analogous to the Icon indicator but each value is associated to a text instead of an icon The types are the same One bit a text represents the On state and...
Page 32: ...the corresponding object There are up to 4 fan speed levels Off Auto Min Med Max The number of levels can be customised as explained later As with climate modes the icons of the successive levels are...
Page 33: ...ermanent Temporary Intermittent Progressive sets the icon representation Note this parameter will remain hidden unless having selected Every indicator is configured separately in Indicator representat...
Page 34: ...to be configured Icon sets the icon to display for each value Enumeration the icon represented depends on the value of the one byte object Disp X Icon Enumeration When selecting this type the followin...
Page 35: ...4 Bytes unsigned Counter 4 Bytes signed Float 2 bytes sets the type of the number indicator Font size Small Big Extra sets the font size of the number Text Figure 22 Display indicator Text 1 bit Type...
Page 36: ...lements 1 6 sets the number of states of the enumerated list For each state the following parameters need to be configured Value 0 255 sets the numerical value assigned to the state Icon sets the text...
Page 37: ...ect Font size Small Big sets the font size of the text Climate Temperature Figure 26 Display indicator Climate Temperature The temperature needs to be updated through the Disp X Climate Temperature tw...
Page 38: ...e Disp x Climate Mode Extended one byte object When selecting this type five checkboxes appear to select which HVAC modes should be available Auto Heat Cool Fan Dry as shown in Figure 28 Representatio...
Page 39: ...Mode Mode Type Extended Climate Fan Figure 29 Display indicator Climate Fan The value should be updated through the Disp x Fan one byte communication object Off Auto 0 enabled disabled defines whethe...
Page 40: ...x 51 100 3 Min 0 33 Med 34 67 Max 68 100 Climate On Off Mode Status Figure 30 Display indicator Climate On Off Mode Status The icon to be represented depends on the value of three one bit objects Disp...
Page 41: ...ode Special Auto Comfort Standby Economy Building Protection disabled enabled five checkboxes to select which of the special modes will be available Representation Text Icon Sets whether the mode is d...
Page 42: ...number of characters allowed up to 6 characters for double boxes for single boxes the limit is 12 characters The font size for some indicators For example the Extra size is not allowed for temperatur...
Page 43: ...Display in the tree on the left Figure 33 Display Thermostat Setpoint Box B This tab contains the following parameters Setpoint Configuration Enable Real Temperature disabled enabled when enabled the...
Page 44: ...Thermostat Fan Box C This tab contains the following parameters Fan Levels 2 3 sets the speed levels that will be available in the indicator Auto Mode disabled enabled sets whether the fan Auto mode w...
Page 45: ...wn in three different styles with solid lines dashed dotted or invisible without division line This configuration may be common to all lines or separate for each as shown in Figure 36 Figure 36 Border...
Page 46: ...ttps support zennio com 46 Figure 37 Display Borders Normal Page Figure 38 Display Borders Thermostat Page Depending on the page style selected in the Configuration tab see section 2 3 1 this screen w...
Page 47: ...zontal configures the middle horizontal lines a1 c1 a2 c2 b1 d1 and b2 d2 Lower lines vertical configures the lower vertical lines c1 c2 c2 d1 and d1 d2 Thermostat Page Horizontal lines configures the...
Page 48: ...e www zennio com 2 4 2 TEMPERATURE PROBE Please refer to the specific user manual Temperature Probe available in the Flat Display v2 product section at the Zennio website www zennio com 2 4 3 MOTION D...
Page 49: ...e Zennio website www zennio com for detailed information about the functionality and the configuration of the related parameters HUMIDITY Flat Display v2 is capable of measure and monitor humidity mea...
Page 50: ...uch Locking 0 Unlock 1 Lock 1 Bit I C W T U DPT_Enable 0 1 General Touch Locking 0 Lock 1 Unlock 10 1 Bit I C W DPT_Ack 0 1 General Cleaning Function 0 Nothing 1 Clean Now 11 2 Bytes I C W T U DPT_Val...
Page 51: ...Btn Ix Light On Off Short press Switch between On and Off 1 Bit C T DPT_Step 0 1 Btn Ix Shutter Stop Step Short press 0 Stop shutter Step up 1 Stop shutter Step down 1 Bit C T DPT_Trigger 0 1 Btn Ix S...
Page 52: ...tn Ix 1 Byte Scaling Value 0 100 1 Byte C T DPT_Scaling 0 100 Btn Ix Fan Control Type Scaling 100 1 Byte C T DPT_Scaling 0 100 Btn Ix Fan Control Type Scaling 50 100 1 Byte C T DPT_Scaling 0 100 Btn I...
Page 53: ...an_Stage 0 255 Btn Ix Fan Control Type Enumeration Auto 1 2 3 4 1 Byte C T DPT_Fan_Stage 0 255 Btn Ix Fan Control Type Enumeration Auto 1 2 3 4 5 1 Byte I C W T DPT_SceneNumber 0 63 Btn Ix Scene Send...
Page 54: ...Long press Left 0 Right 1 1 Bit I C W T DPT_Switch 0 1 Btn Px Two Objects Long press Left 1 Right 0 1 Bit C T DPT_UpDown 0 1 Btn Px Shutter Move Long press Left Down Right Up 1 Bit C T DPT_UpDown 0 1...
Page 55: ...Px Light Dimming Status 0 100 1 Byte C T DPT_Scaling 0 100 Btn Px Fan Control Type Scaling 100 1 Byte C T DPT_Scaling 0 100 Btn Px Fan Control Type Scaling 50 100 1 Byte C T DPT_Scaling 0 100 Btn Px F...
Page 56: ...Px Fan Control Type Enumeration Auto 1 2 3 1 Byte C T DPT_Fan_Stage 0 255 Btn Px Fan Control Type Enumeration Auto 1 2 3 4 1 Byte C T DPT_Fan_Stage 0 255 Btn Px Fan Control Type Enumeration Auto 1 2 3...
Page 57: ...p ax Climate On Off Mode 0 Cool 1 Heat Mode Indicator Is Shown when On Off 1 and Status 0 95 111 127 143 1 Bit I C W T U DPT_Switch 0 1 Disp a Climate On Off Status 0 Halted 1 Running Status icon is s...
Page 58: ...shown 1 Byte I C W T U DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection Disp ax Climate Mode Special Mode Indicator Is Shown 1 Byte I C W T U DPT_Value_1_Ucount 0 255 Disp ax Text Enu...
Page 59: ...unsigned Object numeric value is shown 99 115 131 147 14 Bytes I C W T U DPT_String_UTF 8 Disp a Text from object Received text is shown 99 107 115 123 131 139 147 155 14 Bytes I C W T U DPT_String_U...
Page 60: ...DPT_Enable 0 1 Ix Input Lock 0 Unlock 1 Lock 168 174 1 Bit C T DPT_Switch 0 1 Ix Short Press 0 Sending of 0 1 Bit C T DPT_Switch 0 1 Ix Short Press 1 Sending of 1 1 Bit I C W T DPT_Switch 0 1 Ix Short...
Page 61: ...0 100 2 Bytes C T DPT_Value_2_Ucount 0 65535 Ix Short Press Constant Value Integer 0 65535 2 Bytes C T 9 xxx 671088 64 670433 28 Ix Short Press Constant Value Float Float Value 169 175 1 Byte I C W DP...
Page 62: ...itch 0 1 Ix Long Press Light On Sending of 1 On 1 Bit C T DPT_Switch 0 1 Ix Long Press Light Off Sending of 0 Off 1 Bit I C W T DPT_Switch 0 1 Ix Long Press Light On Off Switching 0 1 1 Byte C T DPT_S...
Page 63: ...1 Ix Presence Trigger Binary Value to Trigger the Presence Detection 188 217 1 Bit I C W DPT_Start 0 1 Ix Presence Slave Input 0 Nothing 1 Detection from slave device 189 218 2 Bytes I C W DPT_TimePer...
Page 64: ...r 1 Bit I C W DPT_Switch 0 1 Tx Special Mode Protection 0 Off 1 On 248 1 Bit I C W DPT_Window_Door 0 1 Tx Window Status Input 0 Closed 1 Open 249 1 Bit I C W DPT_Trigger 0 1 Tx Comfort Prolongation 0...
Page 65: ...O C R T DPT_Switch 0 1 Tx Sx Control Variable Heat PI Control PWM 1 Bit O C R T DPT_Switch 0 1 Tx Sx Control Variable 2 Point Control 1 Bit O C R T DPT_Switch 0 1 Tx Sx Control Variable PI Control PW...
Page 66: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...