ZPS160MPA 

160 mA Power Supply 
ZN1PS-160MPA 

 

 

 

 

 

 

 

 

     

Technical Documentation 

 

© Zennio Avance y Tecnología S.L.                        Edition 4                             Further information 

www.zennio.com

                                 

Page 

1

/

2

 

 

Features 

 

 

Reduced size: 90 x 60 x 35 mm (2 DIN rail units). 

 

KNX system power supply with additional 29VDC output.    

 

ZPS160M  power  supply  generates  and  monitors  the  KNX 
system voltage supply. 

 

Maximum bus KNX current: 160mA. 

 

KNX coil included. 

 

Maximum additional output current: 250mA - I

BUS

 

No device needed when wiring the clamp. 

 

DIN rail mounting (EN 50022), through pressure.  

 

Short-circuit and overload protection. 

 

Conformity with the CE directives (CE mark on the right side).  

 

 
 

 

 
 
 

Installation and connection 

 

 

This KNX power supply must be exclusively installed in a 

35mm DIN rail in a distribution box or an electrical panel. 

 

Ensure  adequate  ventilation  to  prevent  the  range  of 

permissible temperature of the device is not exceeded. 

 

Main  power  must  be  connected  to  L,  N  and  ground 

terminals, in accordance with the schematic represented 
in figure 2. 

 

The  coil  integrated  KNX  output  must  be  connected 

through  a  standard  KNX  connector  as  shown  in  the 
figure 2. 

 

The  additional  output  connection  must  be  connected 

according to the polarity indicated on the clamp. 
 

 

 
 
 

Controls and indicators

 

 

Green LED indicates the status of the device : 

 

 

LED ON: the device is working properly. 

 

LED OFF:  

o

  Short-circuit on the bus output or additional output. Eliminate the short-circuit. 

o

  AC power failure. Check the AC power supply. 

o

  Bus or additional output line overload*.  

 

A LED blinking every few seconds implies a slight BUS or additional output line overload*.  

 

*Reduce the load on the BUS or the additional output line until its total consumption does not exceed the 
maximum current specified.

 

 

Note: To “reset” the bus line, pull out the KNX connector from the power supply for at least 20 seconds. 

 

 

 

 

1

. Main power 

clamp 

2

. Green 

LED 

3

. KNX bus 

connector 

4.

 Additional 

output clamp 

5. 

DIN 

rail 

Figure 1

: ZPS160MPA power supply 

Figure 2

: ZPS160MPA installation and connection 

GND 

230V~ 

50/60Hz 