SAFETY INSTRUCTIONS AND ADDITIONAL NOTES 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each cou ntry. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 The  facility  must  be  equipped  with  a  device  that  ensures  the  omnipolar  sectioning.  Installation  of  a  10 A  mini-circuit-breaker  is 

recommended. To prevent accidents, it must remain open in case of manipulation of the device. 

 The device has a short-circuit protection fuse that, in case of activation, should only be rearmed or replaced by the Zennio technical 

service.  

 This device contains a security short-circuit proof transformer. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 For indoor use only. 

 Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material 

while in use. 

 This device contains a security short-circuit proof transformer. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

https://www.zennio.com/en/legal/weee-regulation. 

 This device contains software subject to specific licences. For details, please refer to http://zennio.com/licenses. 

DALI OUTPUT SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of channels 

Output type / Voltage 

DALI bus / 17 VDC SELV 

Guaranteed current per channel 

128 mA 

Maximum current per channel 

250 mA 

Maximum DALI ballasts per channel 

64 

Maximum length of cable 

300 m (@ 1.5 mm²) 

Short-circuit protection 

YES 

Overload protection 

YES 

Over-voltage protection 

YES 

Connection method 

Screw terminal block (0.5 Nm max.) 

Cable cross-section 

1.5-4 mm² (IEC) / 26-10 AWG (UL) 

 

EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Power supply protection 
fuse 

Voltage 

250 V 

Current 

4 A 

Response type 

F (Fast acting) 

Connection method 

Screw terminal block (0.5 Nm max.) 

Cable cross-section 

1.5-4 mm² (IEC) / 26-10 AWG (UL) 

 

WIRING DIAGRAMS 

Figure 2: Mounting DALI-BOX Interface v2 on 

DIN rail 

Attaching DALI-BOX Interface v2 to DIN rail: 

Removing DALI-BOX Interface v2 from DIN rail:

 

110-240 V

AC

 

50/60 Hz 

Ballast 

(

n

≤64) 

Ballast 1 

 NOTE: 

In  case  of  ballast  replacement,  please,  pay 
attention to the steps defined in the manual. 

 NOTE: 

In  case  of  a  DALI  channel  short  circuit,  the 
device will monitor the DALI channel in order 
to switch  on the output at  full current just as 
the short circuit is removed. 