SAFETY INSTRUCTIONS AND ADDITIONAL NOTES
•
Installation should only be performed by qualified professionals according to the laws and regulations applicable in each cou ntry.
•
Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other
accessories, in case of being installed.
•
The facility must be equipped with a device that ensures the omnipolar sectioning. Installation of a 10 A mini-circuit-breaker is
recommended. To prevent accidents, it must remain open in case of manipulation of the device.
•
The device has a short-circuit protection fuse that, in case of activation, should only be rearmed or replaced by the Zennio technical
service.
•
This device contains a security short-circuit proof transformer.
•
Once the device is installed (in the panel or box), it must not be accessible from outside.
•
For indoor use only.
•
Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material
while in use.
•
This device contains a security short-circuit proof transformer.
•
The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
https://www.zennio.com/en/legal/weee-regulation.
•
This device contains software subject to specific licences. For details, please refer to http://zennio.com/licenses.
DALI OUTPUT SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of channels
1
Output type / Voltage
DALI bus / 17 VDC SELV
Guaranteed current per channel
128 mA
Maximum current per channel
250 mA
Maximum DALI ballasts per channel
64
Maximum length of cable
300 m (@ 1.5 mm²)
Short-circuit protection
YES
Overload protection
YES
Over-voltage protection
YES
Connection method
Screw terminal block (0.5 Nm max.)
Cable cross-section
1.5-4 mm² (IEC) / 26-10 AWG (UL)
EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Power supply protection
fuse
Voltage
250 V
Current
4 A
Response type
F (Fast acting)
Connection method
Screw terminal block (0.5 Nm max.)
Cable cross-section
1.5-4 mm² (IEC) / 26-10 AWG (UL)
WIRING DIAGRAMS
Figure 2: Mounting DALI-BOX Interface v2 on
DIN rail
Attaching DALI-BOX Interface v2 to DIN rail:
Removing DALI-BOX Interface v2 from DIN rail:
110-240 V
AC
50/60 Hz
Ballast
n
(
n
≤64)
Ballast 1
⚠
NOTE:
In case of ballast replacement, please, pay
attention to the steps defined in the manual.
⚠
NOTE:
In case of a DALI channel short circuit, the
device will monitor the DALI channel in order
to switch on the output at full current just as
the short circuit is removed.