Tecla 55
Technical Support:
10
Note:
the first sending after download or bus failure takes place with a delay of
up to 255 seconds, to prevent bus overload. The following sendings march the
period set.
Device Recovery Objects (Send 0 and 1)
[
disabled
/enabled
]: this parameter
lets the integrator activate two new communication objects (“
[Heartbeat]
Device Recovery
”), which will be sent to the KNX bus with values “0” and “1”
whenever the device begins operation (for example, after a bus power failure).
It is possible to parameterise a certain
delay
[
0
…255
][
s
] to this sending.
Figure 5.
Device Recovery Objects.
Note
:
After download or bus failure, the sending takes place with a delay of up
to 6,35 seconds plus the parameterised delay, to prevent bus overload.
Sounds
[
Default
/ Custom
]: sets whether the sound functions (button beeps,
alarm and doorbell) should work according to the pre-defined configuration or
to a user-defined configuration. See section 2.1.3 for details.
Ambient luminosity sensor
[
disabled
/enabled
]: enables setting the ambient
luminosity sensor. When the sensor is enabled, a new tab for its configuration
is shown. See section 2.1.4 for details.
Proximity Sensor
[
disabled
/enabled
]: enables the proximity sensor. This
functionality permits “waking up” the device when detecting presence, see
section 2.1.5.
Time to Consider Inactivity
[
1…
30
…255
][
s
/min/h
]: allows setting a time after
which, if no pulsation or proximity detection has occurred, the LEDs turn off (or
acquire the brightness level configured, see section 2.1.2).
Advanced Configuration
[
disabled
/enabled
]: enables or disables the
“Advanced” tab in the tree on the left. See section 2.1.6 for details.