SAFETY INSTRUCTIONS
•
Installation should only be performed by qualified professionals according to the laws and regulations applicable in each cou ntry.
•
Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other
accessories, in case of being installed.
•
Once the device is installed (in the panel or box), it must not be accessible from outside.
•
Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material
while in use.
•
The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
http://zennio.com/weee-regulation.
OUTPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of outputs
2
Output type / Disconnection type
Potential-free outputs through bistable relays with
tungsten pre-contact / Micro-disconnection
Rated current per output
AC 16(6)A @ 250VAC (4000VA)
DC 7A @ 30VDC (210W)
Maximum load
per output
Resistive
4000W
Inductive
1500VA
Maximum inrush current
800A/200μs
165A/20ms
Connections in adjacent outputs
Possibility of connecting different phases. It is not
allowed to connect power supplies of different
order, SELV with NO SELV, in the same block
Total maximum current in device
20A
Short-circuit protection
NO
Overload protection
NO
Connection method
Screw terminal block
Cable cross-section
0.5-4mm² (IEC) / 20-12AWG (UL)
Outputs per common
1
Maximum response time
10ms
Mechanical lifetime (min. cycles)
3 000 000
Electrical lifetime (min. cycles)
1
100000 @ 8A / 25000 @ 16A (VAC)
¹ Lifetime values could change depending on the load type.
INPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of inputs
5
Inputs per common
1
Operation voltage
+3.3VDC in the common
Operation current
1mA @ 3.3VDC (per input)
Switching type
Dry voltage contacts between input and common
Connection method
Screw terminal block
Cable cross-section
0.5-2.5mm² (IEC) / 26-12AWG (UL)
Maximum cable length
30m
NTC probe length
1.5m (up to 30m)
NTC accuracy (@ 25°C) ²
±0.5°C
Temperature resolution
0.1°C
Maximum response time
10ms
² For Zennio temperature probes.
⚠
In order to ensure the expected status of the
relays, please check that the device is connected to
the KNX bus before energizing the power circuit.
WIRING DIAGRAMS
Figure 2: Wiring example (from left to
right, and up to down): 2 loads, 2 loads
connected to different phases and shutter
* In case of using ZN1IO-DETEC-P sensor, its micro switch number 2 must be in
Type B position.
** Zennio temperature probe or any NTC with known resistance values at three points in the range [-55, 150ºC].
INPUTS CONNECTION
Any combination of the following
accessories
is allowed on the inputs:
Zennio temperature
probe.
Up to two motion sensors
can be plugged into the
same device input (parallel
wiring)
Screw
terminal
for
connecting Zennio motion
sensors*
Temperature Probe**
Motion Sensor
Switch/Sensor/
Push button
C IN
C IN
C I
C IN
C IN
C IN
C I
C IN
C IN
C IN
C I
C IN
Attaching MINiBOX 25 v2 to DIN rail:
Removing MINiBOX 25 v2 from DIN rail:
A1
A2
M
N
L
A1
A2
N
L
L1
L2
C IN
C IN
C I
C IN
A1
A2
N
L1
L1
L2
L2
A1
A2
M
N
L
A1
A2
N
L
L1
L2
C IN
C IN
C I
C IN
A1
A2
N
L1
L1
L2
L2