Technical Documentation   

© Zennio Avance y Tecnología S.L.                    Edition 3                             Further information 

www.zennio.com

                             

Page. 

2

 / 

2

 

 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
 
 
 
 
 
           

   

 
 
 
 

  
 
                    

 
 
 
 

Any combination of the next 

accessories

 is allowed in the inputs:

 

 
 
 
 
 
 
        
 
              
 
 
 
 
 
 
 
 

SAFETY INSTRUCTIONS

 

  Do not connect Main Voltage (230 V) or any other external voltages to any point of the BUS.  

Connecting an external voltage might put the entire KNX system at

 

risk. 

  Flexible cable with crimping terminals or rigid cable without terminals must be used for output connection.  

  Make sure during the installation that there is always sufficient insulation between the mains voltage 230V and the bus or 

the extension inputs. 

  Once the device is installed, the output terminal should not be accessible.  

OUTPUTS SPECIFICATIONS AND CONNECTIONS

 

Contact type 

Potential free outputs through bistable 
relays with tungsten pre-contact. 

Disconnection type 

Micro-disconnection 

Rated current by output 

16A * 250V AC (4000 VA)        

16A * 30V DC (480W) 

Maximum inrush current  

800A/200

μs (fluorescent lamps) 

165A/20ms (resistive lamps) 

Dropping voltage 

Negligible 

Outputs per common (channel) 

1 individual output 

Different phases connection 

Possibility to connect different phases in 
adjoining outputs 

Maximum current  

60A 

Connection type 

Terminal block (screw)  

Recommended cable section 

0.25 mm² to 4 mm²  (26-10 AWG) 

Cable type 

Stranded or solid wire 

Maximum response time 

50 ms  

Contact type 

Potential free outputs through bistable 
relays with tungsten pre-contact. 

No. of automatic cycles (A) 
per automatic action 

Mechanical 
(min) 

3 million operations (60cpm) 

Electrical 
(min.)

 

100.000 cycles at Max. current (6cpm 
and resistive load) 

INPUT SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of inputs per common 

Input voltage 

+3.3V DC for the common  

Input current 

1.0mA @ 3.3V DC (each input) 

Input impedance 

Aprox. 3.3kΩ 

Switching type 

Dry  voltage  contacts  between 
input and common 

Connection method 

Cable screw terminal  

Max. cable length 

30 m. 

NTC probe length 

1.5 m. 

NTC accuracy (@ 25ºC) 

0.5ºC 

Temperature measure precision 

0.1ºC 

Cable cross-section  

0.15 mm² to 2.5 mm² (26-12 AWG) 

Response time  

Max 10ms. 

Attaching MAXinBOX66 to DIN rail: 

Removing MAXinBOX66 from DIN rail:

 

Figure  2

:  (From  up  to  down  and 

from  left  to  right)  Terminal  block  1 
wiring examples for shutter channel, 
outputs with same phase or outputs 
with different phases

.

 

 

Temperature 
probe 
references: 

ZN1AC-NTC68E 
ZN1AC-NTC68F 
ZN1AC-NTC68S 

 

Up to two motion sensors 
can be plugged into the 
same MAXinBOX66 input 
(parallel wiring) 

 

Motion sensor cable screw 
terminal. 

Motion sensor references: 

ZN1IO-DETEC-P

(1)

 

ZN1IO-DETEC-X 

 

Temperature Probe 

 

Motion Sensor 

 

Switch/Sensor/ 

Push button 

 

WIRING AND ASSEMBLY DIAGRAMS

 

 

(

*

)

 

In order to guarantee the correct functioning of relays when several outputs are controlled jointly,  it is necessary to place the 

actuator as close as possible to the KNX power supply. A 29VDC KNX power supply is recommended.

 

 

 

(1) The micro switch number 2 in the ZN1IO-DETEC-P 

must be in Type B position

 to 

work properly. 

 

Motion sensor reference: 

ZN1IO-DETEC 
ZN1IO-DETEC-N 
ZN1IO-DETECT-P

(1)

 