OUTPUTS SPECIFICATIONS AND CONNECTIONS 

Contact type 

Potential free outputs through bistable relays. 

Disconnection type 

Micro-disconnection 

Rated current by output 

8A (4A) * 250V AC (2000 VA)        

8A (4A) * 30V DC (240W) 

Outputs per common  

3 (fan outputs) or 1 (pipe outputs)  

Different phases connection 

Possibility to connect different phases in adjoining channel outputs 

Maximum current  

32A per block  

Maximum power 

Resistive load 

2000W 

Inductive load 

1000VA 

Connection type 

Screw terminal block  

Recommended cable section 

0.5mm² to 4mm² (26-10AWG) 

Cable type 

Stranded or solid wire. 

Maximum response time 

50ms  

Expected life 

Mechanical (min)  1 million operations (180cpm) 
Electrical  (min) 

50.000 cycles (6cpm/ resistive load) 

WIRING AND ASSEMBLY DIAGRAMS 

Figure 2. 

FAN COIL wiring examples with the same and with different phases

 

Attaching MAXinBOX FANCOIL 4CH2P to DIN rail: 

Removing MAXinBOX FANCOIL 4CH2P from DIN rail: 

Figure 3. MAXinBOX FANCOIL 4CH2P DIN-rail assembly

 

SAFETY INSTRUCTIONS 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of 
other accessories, in case of being installed. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water and do not cover it with clothes, paper or any other material while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

http://zennio.com/weee-regulation. 

 In order to ensure the expected 

status  of the  relays, please  check 
that the device is connected to the 
KNX  bus  before  energizing  the 
power circuit.

 