OUTPUTS SPECIFICATIONS AND CONNECTIONS
Contact type
Potential free outputs through bistable relays.
Disconnection type
Micro-disconnection
Rated current by output
8A (4A) * 250V AC (2000 VA)
8A (4A) * 30V DC (240W)
Outputs per common
3 (fan outputs) or 1 (pipe outputs)
Different phases connection
Possibility to connect different phases in adjoining channel outputs
Maximum current
32A per block
Maximum power
Resistive load
2000W
Inductive load
1000VA
Connection type
Screw terminal block
Recommended cable section
0.5mm² to 4mm² (26-10AWG)
Cable type
Stranded or solid wire.
Maximum response time
50ms
Expected life
Mechanical (min) 1 million operations (180cpm)
Electrical (min)
50.000 cycles (6cpm/ resistive load)
WIRING AND ASSEMBLY DIAGRAMS
Figure 2.
FAN COIL wiring examples with the same and with different phases
Attaching MAXinBOX FANCOIL 4CH2P to DIN rail:
Removing MAXinBOX FANCOIL 4CH2P from DIN rail:
Figure 3. MAXinBOX FANCOIL 4CH2P DIN-rail assembly
SAFETY INSTRUCTIONS
Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country.
Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of
other accessories, in case of being installed.
Once the device is installed (in the panel or box), it must not be accessible from outside.
Keep the device away from water and do not cover it with clothes, paper or any other material while in use.
The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
http://zennio.com/weee-regulation.
⚠
In order to ensure the expected
status of the relays, please check
that the device is connected to the
KNX bus before energizing the
power circuit.