MAXinBOX FANCOIL 4CH2P 

 
4 channel two pipes fan coil controller 
ZCL-4XFC2P       

 

 

 

 

 

 

                                          

Technical Documentation

 

 

FEATURES

 

  Up to four blocks to control 2-pipe fan coil units. 

  Manual  output  operation  with  push  button  and  LED  status 

indicator. 

  Logical functions included. 

  Output timing facilities. 

  Total data saving on power failure. 

  Size 90 x 60 x 140 mm (8 DIN units). 

 

DIN rail mounting (EN 50022), through pressure. 

  No external power supply required other than the bus. 

  Integrated KNX BCU. 

  Possibility to connect different phases in adjoining outputs. 

  Conformity with the CE directives (CE-mark on the right side). 

 

 

 

 
 
 

 

 

 

 

 

 
 
 
 
 

 
 
 

GENERAL SYSTEM SPECIFICATIONS 
CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX 
Supply 

Voltage (typical) 

29VDC SELV 

Voltage range 

21…31V DC 

Maximum 
consumption 

Voltage 

mA 

mW 

29VDC (typical) 

7.5 

217,5 

24VDC

(1)

 

10 

240 

Bus connection 

Typical bus connector TP1 for rigid cable 0.80mm Ø 

External power supply 

No 

Operation temperature 

from 0ºC to +55ºC 

Storage temperature 

from -20ºC to +70ºC 

Operation humidity 

5 to 95% RH (no condensation) 

Storage humidity  

5 to 95% RH (no condensation) 

Complementary characteristics 

Class B 

Protection class 

II 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (EN 50022) 

Response on KNX bus failure 

Data saving and output status change according to programming. 

Response on KNX bus restart 

Data recovering and output status change according to programming. 

Operation indication 

Programming LED indicates programming mode (red) and test mode (green). 
Output status LED indicators reflect current output state. 

Weight 

440g

 

PCB CTI index 

175V 

Housing material 

PC FR V0 halogen free

 

(1)

 Maximum consumption in the worst case scenario (KNX Fan-In model)

 

Programming/test button

: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe 

mode.

 

If this button is held for more than 3 seconds, the device enters the test mode. 

 

Programming/Test LED: 

programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual 

mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking 
sequence.

 

 

1

. Upper outputs

 

2

. Lower outputs

 

3

.Programming/Test LED

 

4

.KNX connector

 

5

.Programming/Test button

 

6

.Output control button

 

7

.Output status LED indicator

 

 

Figure 1. 

MAXinBOX FANCOIL 4CH2P

 

6