KLIC-FJ vT
Technical Support:
33
209
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] On/Off (Status)
0 = Off; 1 = On
210
1 Bit
O
C R - T -
DPT_Bool
0/1
[AC] Internal Error: Control
Unable to Control the AC
211
1 Bit
O
C R - T -
DPT_Bool
0/1
[AC] Internal Error: Communication
Unable to Set AC Communication
212
1 Bit
O
C R - T -
DPT_Bool
0/1
[AC] AC Unit Error: Active Error
AC Unit Error
213
14 Bytes
O
C R - T -
DPT_String_ASCII
[AC] AC Unit Error: Error Code
See AC Unit Manual
214
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
0 % = Automatic; [0.4...25.1] % =
S1; [25.5...50.2] % = S2;
[50.6...75.3] % = S3; [75.7...100]
%= S4
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
0 % = Automatic; [0.4...33.3] % =
S1; [33.7...66.7] % = S2;
[67.1...100] % = S3
215
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
(Status)
Automatic = 0 %; S1 = 25 %; S2 =
50 %; S3 = 75 %; S4 = 100 %
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
(Status)
Automatic = 0 %; S1 = 33.3 %; S2 =
66.7 %; S3 = 100 %
216
1 Bit
I
C - W - -
DPT_Enable
0/1
[AC] Fan: Automatic
0 = Automatic Off (Speed 1); 1 =
Automatic On
1 Bit
I
C - W - -
DPT_Enable
0/1
[AC] Fan: Automatic
0 = Automatic On; 1 = Automatic Off
(Speed 1)
217
1 Bit
O
C R - T -
DPT_Enable
0/1
[AC] Fan: Automatic (Status)
0 = Automatic On; 1 = Automatic Off
1 Bit
O
C R - T -
DPT_Enable
0/1
[AC] Fan: Automatic (Status)
0 = Automatic Off; 1 = Automatic On
218
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing
0 = Swing On; 1 = Swing Off
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing
0 = Swing Off; 1 = Swing On
219
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing
(Status)
0 = Swing On; 1 = Swing Off
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing
(Status)
0 = Swing Off; 1 = Swing On
220
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing
0 = Swing Off; 1 = Swing On
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing
0 = Swing On; 1 = Swing Off
221
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing (Status)
0 = Swing On; 1 = Swing Off
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing (Status)
0 = Swing Off; 1 = Swing On
222
1 Bit
I
C - W - -
DPT_Step
0/1
[AC] Horizontal Flaps: Step Control
0 = No action; 1 = Step
223
1 Bit
I
C - W - -
DPT_Step
0/1
[AC] Vertical Flaps: Step Control
0 = No action; 1 = Step
224
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AC] Horizontal Flaps: Percentage
Control
[0.4...25.1] % = P1; [25.5...50.2] %
= P2; [50.6...75.3] % = P3;
[75.7...100] %= P4
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AC] Horizontal Flaps: Percentage
Control
0 % = Swing; [0.4...25.1] % = P1;
[25.5...50.2] % = P2; [50.6...75.3]
% = P3; [75.7...100] %= P4