WIRING DIAGRAMS
Figure 2: Wiring example (from top to bottom and left to right): 2 loads, 2 loads connected to different phases, shutter channel,
fancoil three-speed fan, fancoil three-point valves and fancoil open/close valves.
* In case of using ZN1IO-DETEC-P sensor, its micro switch number 2 must be in
Type B position
.
** Zennio temperature probe or any NTC with known resistance values at three points in the range [-55, 150ºC].
INPUTS CONNECTION
Any combination of the following
accessories
is allowed in the inputs:
Zennio temperature
probe.
Up to two motion sensors
can be plugged into the
same device input (parallel
wiring)
Screw
terminal
for
connecting Zennio motion
sensors*.
Temperature Probe**
Motion Sensor
Switch/Sensor/
Push button
INPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of inputs
12
Inputs per common
4
Operation voltage
+3.3VDC in the common
Operation current
1mA @ 3.3VDC (per input)
Switching type
Dry voltage contacts between input and common
Connection method
Screw terminal block
Cable cross-section
0.5-2.5mm² (IEC) / 26-12AWG (UL)
Maximum cable length
30m
NTC probe length
1.5m (up to 30m)
NTC accuracy (@ 25°C) ²
±0.5°C
Temperature resolution
0.1°C
Maximum response time
10ms
² For Zennio temperature probes.
⚠
In order to ensure the expected status of the
relays, please check that the device is
connected to the main power supply before
energizing the power circuit.
For a 4-pipe fancoil, the cooling valve should
always be connected on the left side and the
heating valve on the right side. Before the start-
up of the device, it must be assured that the valve
is completely closed.
Outputs that are not being used for valve control
can be used as individual outputs or shutter
channels.
Wiring the fancoil to the outputs of the lower side
of the device is similar to that of the upper outputs
(E1=A1, E2=A2, F1=B1, ...).
OPEN
CLOSE
OPEN
CLOSE