ALLinBOX 1612 v2
Technical Support:
31
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the IR remote control pushbuttons. Orders received through communication objects will
be ignored, with independence of the channel or the output they are addressed to.
Depending on whether the output has been parameterised as an individual output or as
part of a shutter channel or a
fan coil
module, the reactions to the button presses will
differ.
Individual output
: short or long pressing the button will commute the on-off
state of the relay.
Shutter channel
: pressing the button will make the shutter drive move
upward or downward (depending on the button) until the button is released
again, thus ignoring the position of the shutter and the parameterised times.
Note
:
after leaving the Test On mode, the status objects will recover the
values they had prior to entering Test On. As the device is never aware of the
actual position of the shutter (as the shutter drive does not provide any
feedback), these values may not show the real position. This can be solved
by performing a complete move-up or move-down order, or by calibrating the
shutter position in the Test On mode until it matches the status objects.
Fan Coil module
: the behaviour will be different for the buttons identified as
fan and the identified as valve (see Table 1):
➢
Fan
: a short or long press will switch the relays to set the selected speed,
unless it matches the current speed
– in such case all the relays will be
opened (speed 0).
Note
:
the behaviour of the relays will depend on the parameterisation, i.e.,
on the number of fan speeds, on the delay between switches and on
whether the control type is accumulation or switching.
➢
Valve
: a short or long press will switch the current status of the relay and
therefore of the valve.