TheWSserieshasbeenapprovedwithaflowsensitivityclassU0/D0.
However,toachievethebestmeasurementresults,werecommend
observingnationalregulationsandrecognisedrulesoftechnology.
■
ForWSseriesisrecommendedastraightinletsectionofatleast5xDN.
■
Ideally,atleast2xDNshouldbeavailableastheoutletsection.
■
Beforeinstallingthemeter,thepipingmustbethoroughlyflushedout.
■
Thepipediametershouldnotbereduced,directlyinfrontandbehind
the meter.
■
Flangegasketsmustnotextendintothepipe.
■
Itmustbeensuredthattheflowdirectionofthemetermatchesthatof
the pipe.
■
Valvesorotherflowregulatorsshouldbeinstalled,wherepossible,
behindthemeter.
■
Themetershouldbeinstalled,wherepossible,atthehighestpointof
thepipeinstallationsothatairbubblesarenotabletoforminthemeter
andthepipeisalwayscompletelyfilled.
■
Ifnecessary,themetershouldbeprotectedbyacorrespondingfilter,
sothatnoforeignparticles,suchasstonesorsand,areflushedintothe
measuringinstrumentandcausedamage.
■
Themetermustbeprotectedagainstpressuresurgesinthepipe
network.
■
Themaximumwatertemperaturemustnotexceedthepermissible50
°Cforcoldwater.
■
Inordertopreventdamagetothemeasuringinsertcausedbypressure
surges,thepipemustbeslowlyfilledfollowinginstallation.
■
Itmustbeensuredthatthemeterisinstalledinade-energisedstate
inthepipe.Inthecaseofaninstallationthatisnotde-energised,the
housingofthemeasuringinstrumentcanbedamagedandwatermay
escape.
■
Thepipelinepressuremustnotexceedthemaximumworkingpressure
ofthemeter,asthiscanleadtoleaksanddamageofthemeter.
■
Topreventthedisassemblyofthemeterwerecommendtosecurethe
connectioninterfacewithasafetydevice(adhesivelabel,seal,etc.).
■
AllserieshasbeenapprovedwithaflowsensitivityclassU0/D0(noinlet
outletsectionrequired).
■
Allseriesarenotapprovedforbackflowmeasuring.
Installation instructions for the replacement of the metrological unit
■
Theexchangeofexchangeablemetrologicalunits(measuringinsert
shouldonlybeperformedbytrainedspecialiststaff.
■
Beforechangingthemeasuringinsert,thepipemustberinsedcarefully
shutoffthepressuresideandemptythepipe.
■
Thecomplianceoftheinterfacesmarkingonthemeasuringandatthe
specifiedinterface(body)(WS1)mustbechecked.
■
Afterdisassemblyofthemeasuringinsertoldgaskets/sealsmustbere
-
moved.Thesealingsurfacesmustbecleanedandcheckedfordamage.
■
Itisimportanttoensurethattheinletareaisfreeofdeposit,beforea
newmetrologicalunitisinstalled,becauseasthesecanleadtodevia
-
tions of the measurement result.
■
Useonlythegenuineseals,whicharedeliveredtogetherwiththe
measuringinsert.Thesehavetobecheckedpriortoinstallationfor
damageandfit.
■
Whenusinglubricants/assemblypastese.g.fortheseals,itmustbe
ensuredthatthesearesuitableforcontactwithdrinkingwater.
■
Tightenthescrewsofthemeasuringunitevenlycrosswise(M12:DN50–
DN100=60Nm;M20:DN150–DN200=100Nm).
■
Topreventthedisassemblyofthereplacablemeasuringinsert,itmust
beconnectedwiththeconnectioninterface(housing)byasealingwire.
Thedeclarationofconformityisincludedinthedelivery.Thelatestinforma
-
tiononthisproductcanbecalledupfrom
www.zenner.com
Remark
Thisinstallationmanualisintendedforqualifiedspecialistsonly.Basic
installationstepsarethereforenotdescribed.
Permissible installation positions
TheWSseriesisintendedforinstallationinthehorizontalpositiononly.
Installation instructions
WSD/WSDE