background image

Measurement and Transmission Interval

The sensor does multiple measurements per minute and stores the 
current CO

2

 value in ppm (parts per million) every 15 minutes. After 45

 

minutes, the sensor sends the last three stored CO

2

 values via

 

LoRaWAN®. If the measuring range is exceeded, the battery is too low or

 

a hardware error is detected, the sensor immediately sends a status

 

packet.
Historical data can be viewed and thresholds can be set via the respective 
IoT platform.

Screen Saver

If the device is charged and is not being operated for 4 minutes, the device 
switches to screen saver mode to protect the display from burning out. 

During this process the current display of CO

2

 value moves back and forth 

on the screen.

Turn Off the Display

Briefly press the power button on the back of the device to switch off the

 

display. The LED indicator and data transmission remain active. The display

 

cannot be switched off if a CO

2

 content > 1000ppm is measured.

Power Off

Press the power button on the back of the device for 4 seconds to switch off 
the device.

Energy Saving Mode

When the device is being operated via the integrated battery, the display 
automatically switches off after 4 minutes without operation. This saves 
energy and achieves a longer battery life.

 

 
The CO

2

 concentration can always be checked on the LED indicator during 

this time.

Reset Network Settings

If the device cannot connect to the LoRaWAN® network, you can reset the 
network settings. To do so press and hold the concave bar on the top of 

the product for at least 8 seconds until the signal icon on the screen starts 

flashing. The network has been reset successfully.

Reset Sensor

If the sensor measures abnormal CO

2

 levels, you can reset the sensor using 

a manual calibration. To do this, press and hold the concave bar on the 
top of the device and the power button on the back of the device simul

-

taneously for at least 8 seconds.
Now the device will take about 12 minutes to reset and reinitialize the 
sensor.

 

 

Notice:
Perform this procedure out in fresh air or directly next to an open windo 

 

Do not breathe in the direction of the device.

Evaluation of the CO

2

 Measured Values

The measuring ranges can be set individually via LoRaWAN®-Downlink.

Measuring range

Evaluation

LED Color

< 800 ppm

normal

green

800 ‒ 999 ppm

slightly high

yellow

1.000 ‒ 1.399 ppm

high

purple

> 1.399 ppm

very high

red

Reviews: