MARINE MASTER CLOCK
User Manual
Alarm list
The following alarms are available
Type of alarm
Al
ar
m
code
Indication
Reason for alarm
Action
NO RADIO
30 Red alarm LED lit.
General alarm relay activated.
The Master Clock
has
not
been
synchronized within
the alarm limit.
Check the external
synchronization source. If
no external source is used
inactivate the alarm. See
special function/ setup
sync. source page 36.
UF LOW
52 Red alarm LED lit.
General alarm relay activated.
Impulse voltage below
alarm limit.
Remove connected clocks
and clear the alarm. If OK,
check clocks and wiring.
SHORT CIRCUIT
53 Red alarm LED lit.
General alarm relay activated.
Short circuit on impulse
amplifier.
Remove short circuit.
If OK, clear the alarm.
CURRENT LOW
61 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 1 is below
alarm limit.
Check output
connections. If OK, clear
the alarm.
CURRENT LOW
62 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 2 is below
alarm limit.
Check output
connections. If OK, clear
the alarm.
CURRENT LOW
63 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 3 is below
alarm limit.
Check output
connections. If OK, clear
the alarm.
CURRENT LOW
64 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 4 is below
alarm limit.
Check output
connections. If OK, clear
the alarm.
CURRENT HIGH
71
Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 1 is above
alarm limit.
Check output load.
If OK, clear the alarm.
CURRENT HIGH
72 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 2 is above
alarm limit.
Check output load.
If OK, clear the alarm.
CURRENT HIGH
73 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 3 is above
alarm limit.
Check output load.
If OK, clear the alarm.
CURRENT HIGH
74 Red alarm LED lit.
General alarm relay activated.
Impulse current on
output no. 4 is above
alarm limit.
Check output load.
If OK, clear the alarm.
CURRENT HIGH
75 Red alarm LED lit.
General alarm relay activated.
(Remark: Alarm 75 is only used
in a 3-wire Forward/Reverse
system.)
Impulse current on
output no. 4 is above
alarm limit.
Check output load.
If OK, clear the alarm.
WESTERSTRAND URFABRIK AB