High Performance Output Filter – IP00 Series
IM00168
+B Terminal
The ZENER 8000 +B/BR+ terminals are supplied as a factory fitted option. The following table lists the part numbers
corresponding to ZENER 8000 inverters from 15A to 490A.
Fuse Data:
The fuse is a fast acting type, rated 30A 600VDC with a cartridge size 38.1 x 10.31mm. Do not substitute other types.
Description
Zener Part Number
Replacement Fuse, 30A 600VDC
AP18080
NOTE:
THE IP00 HIGH PERFORMANCE OUTPUT FILTER requires connection to the ZENER 8000 (+) DC bus. The factory
fitted option provides a fused terminal in the ZENER 8000 for this purpose.
Cable Size:
The minimum cable size used for the B should be no less than the size required for the protective earth
conductor in the inverter installation (Chassis A & B models) or 30A for models (Chassis C & D) fitted with a fused
terminal. For supply protection, cable size and electrical isolation information, refer to the ZENER 8000 Installation
Manual.
Chassis C and D:
Chassis C & D include a 30Amp fuse on the +B terminal. This allows a smaller cable size to be used. The recommended
minimum cable size is 6mm2 (for UL508C compliance) or according to applicable wiring codes.
The fuse is intended provide thermal protection for the B+ wire in the event of a cable or filter fault condition.
Description
Part Number
Internal Fuse
ZENER 8000 DC Bus Terminal Kit for Chassis A - fitted
n/a
n/a
ZENER 8000 DC Bus Terminal Kit for Chassis B - fitted
AF03101
n/a
ZENER 8000 DC Bus (+ only) Terminal Kit for ChC with Fuse - fitted
AF08107
30A
ZENER 8000 DC Bus (+ only) Terminal Kit for ChD with Fuse - fitted
AF08108
30A