Warning
Fire Suppression System
Information
Before working within the Zellabox
ALWAYS
ensure you follow
these steps:
1.
Turn key switch to manual
2.
Isolate both zones 1 and 2 by pressing the isolate zones buttons
located on the front panel
3.
A beeping sound will continue intermittently as a reminder
4.
Once you have completed work within the MDC and you are ready to
close the doors press the isolate buttons 1 and 2 once more
5.
Turn the key switch back to the automatic position
6.
The Pyrorack should return to normal status
19