8.3 CONDENSATE DISCHARGE SYSTEM
On a minimum of a monthly basis, the operation of the automatic drain should be
checked. The drain should be removed and cleaned as well to ensure no debris
from the system is trapped inside the strainer. Figure 5 illustrates the drain
assembly. To clean the drain, turn the Isolation Valve to the off position. Be sure
the valve is depressurized. Carefully remove the Strainer End Cap and remove the
Strainer. Clean the Strainer and remove any debris that is evident in the valve.
Replace the Strainer and reinstall the Strainer End Cap. Carefully open the
isolation valve and inspect the Strainer End Cap for leaks. Tighten as required.
If your dryer is installed without a drain isolation valves (filter stop), failure to depres-
surize the dryer may result in serious injury. Do not remove the drain valve without
depressurizing the unit.
FIGURE 5
DRAIN DETAIL
DRAWING 737486