43
Troubleshooting worksheet
This form MUST be submitted to Zehnder Rittling Sales Support staff prior to shipment of replacement parts.
Date
installed
Model
number
Technician
Serial
number
Power
Air
side
Fan
motor
volts
Fan
motor
amps
Refrigeration
side
Compressor
volts
Total
volts
Compressor
amps
Total
amps
Note:
All Zehnder Rittling Water Source Heat Pumps are pre-charged and factory run tested. The R410A refrigerant charge used on all unit chassis models
is weighed into exact amounts, refrigeration gauges should only be attached as a last resort. Failure to replace lost charge may result in loss of capacity/
efficiency and equipment life.
Cooling Cycle
Air
side
Inlet air
temperature
(return) °F
Outlet air
temperature
(supply) °F
Water
side
Water inlet
temperature
°F
Pressure
psig
Water outlet
temperature
°F
Pressure
psig
Refrigeration
side
Compressor
suction side
temperature °F
Compressor
discharge side
temperature °F
Compressor
suction side
pressure psig
Compressor
discharge side
pressure psig
Expansion valve
temperature,
entering valve °F
Expansion valve
temperature,
leaving valve °F
Heating Cycle
Air
side
Inlet air
temperature
(return) °F
Outlet air
temperature
(supply) °F
Water
side
Water inlet
temperature
°F
Pressure
psig
Water outlet
temperature
°F
Pressure
psig
Refrigeration
side
Compressor
suction side
temperature °F
Compressor
discharge side
temperature °F
Compressor
suction side
pressure psig
Compressor
discharge side
pressure psig
Expansion valve
temperature,
entering valve °F
Expansion valve
temperature,
leaving valve °F
Note: Before recording above data, each cycle should be run for 10-15 minutes or until stable.