14 - EN
3. Installation conditions
In order to determine whether the unit
can be installed in a certain area, the
following aspects must be taken into
account:
�
Check whether the admissible load (kg/
m2) of the roof or floor is sufficient to
bear the given weight of the unit;
�
The system must be fitted to allow
sufficient room around the unit for the
air duct connections, condensation
drain as well as for carrying out
maintenance activities like a filter
exchange;
To ensure components can be
replaced, at least one casing‘s
width of free space is required.
�
The condensation must be drained off
frost-free, at a gradient and incorporate
an air seal (U-bend or dry siphon);
�
The room must offer the following
provisions:
- Air duct connections;
- Electrical power connection;
-
Provisions for the condensation
drain;
- Facilities for battery or batteries.