![Zehnder Rittling ComfoAir Q TR Manual Download Page 9](http://html2.mh-extra.com/html/zehnder-rittling/comfoair-q-tr/comfoair-q-tr_manual_3345715009.webp)
8 - EN
EN - 9
ComfoAir Q 600
1
2
3
4 5
6
7
8
9
10
11
12
0.75
1.00
1.25
1.50
45
48
51
54
57
0
50
100
150
200
250
0
50
100
150
200
250
300
350
400
450
500
550
600
Ps
t
(P
a)
Qv (m³/h)
ComfoAir Q600 GB ST
SFP (W/l/s)
Lw (dB[A])
intended work area
Qv
m³/h
Pst
Pa
P
W
cos
φ
-
SFP
Wh/l/s
Lw, supply
dB(A)
Lw, extract
dB(A)
Lw, casing
dB(A)
1
250
25
28
0.48
0.40
54
43
43
2
300
25
44
0.51
0.53
56
45
45
3
350
50
72
0.54
0.74
59
48
48
4
400
50
97
0.55
0.87
62
50
50
5
420
50
107
0.56
0.92
63
51
51
6
450
100
143
0.57
1.15
65
53
53
7
500
100
176
0.59
1.27
68
55
55
8
600
100
254
0.61
1.53
73
59
60
9
450
150
162
0.58
1.29
66
53
54
10
450
200
180
0.59
1.44
67
54
55
11
500
200
215
0.60
1.55
70
56
57
12
600
200
296
0.61
1.77
75
60
61
Lw in dB(A) reference 10ˉ¹²W
Casing radiation measured according to ISO 3741:2010
Supply noise and extract noise measured according ISO 5135:1997 (values include end duct correction)
SFP calculated using data measured according EN13141-7:2010
cos phi with pre heater switched off (if present)
When the automated bypass control is active the maximum air flow is restricted.