7

2.5        Access for Maintenance 

            

Footprint of ComfoAir 155 CM

2.6        Condensate Drain 

            

2.6.1           It is important that any condensate MUST be drained away.

                  
                  • The ComfoAir 155 CM unit is provided provided with a condensate drain located at the side of the unit 
                  

(See Figures 6-8)

and can be rotated for ease of connection.   

                  The drain plug allows a condensate drain hose (21.5mm diameter) to be push connected and solvent
                  welded/sealed. Please ensure a water tight seal is achieved.

2.6.2           The drain must have a 5º fall and can either be chased into the wall or run downwards from the unit into the 

                  nearest waste water network. Ensure that steps are taken to minimise the risk of mechanical damage to the 
                  drainage pipe work.

                  

IMPORTANT NOTE: The condensate drain must incorporate a waterless 

            trap or U bend to create an air block and avoid leakage of smells back 

            into the unit. If the unit is installed within a loft space, please ensure 

            that the condensate drain is insulated to prevent against freezing.

2.6.3           In some instances, a condensate connecting point will already be provided as part of the building design. 

                  The position of this point, relative to where the unit is to be installed should be checked for any connection 
                  misalignment and any necessary adjustment made before proceeding any further.

500mm

250mm

TopView

Figure 5

Note:

There should be no movement once 
correctly located and the filters 
should be accessible from easily 
removing the panels on the front of 
the unit 

(See Section 4.1.9, 

Homeowner Guide). 

Side View

Summary of Contents for ComfoAir 155 CM

Page 1: ...ComfoAir 155 CM Mechanical Ventilation with Heat Recovery Installation Instructions CA155CM GB...

Page 2: ...2 0 Installation Instructions 4 General Preparation 4 Configuration 5 Mounting 6 Access for Maintenance 7 Condensate Drain 7 Ducting Guidelines 8 Electrical 9 Wiring the Unit 10 Connecting to the BMS...

Page 3: ...ow and high option ZGRC1 Hardwired boost and system status controller switching between low and high option ZGS1 Hardwired switch providing switching between low AUX and high option 1 1 5 Packaging in...

Page 4: ...ired for compliance with local Building Regulations 2 1 2 Installation of the unit should be in accordance with the current editions of Building Regulations NHBC Compliance Guide and BS7671 IEE Wiring...

Page 5: ...on 2 5 Access for Maintenance 2 2 4 The unit can be configured for right and left hand installation at a touch of a button by following the steps within the Commissioning Wizard See Section 3 1 4 Comm...

Page 6: ...e 1 and loosely fit four screws within each slot at the inner nearside point This will allow the bracket to be slotted inwards to secure the unit 2 4 3 The unit fixes to the ceiling bracket by slottin...

Page 7: ...k of mechanical damage to the drainage pipe work IMPORTANT NOTE The condensate drain must incorporate a waterless trap or U bend to create an air block and avoid leakage of smells back into the unit I...

Page 8: ...must be insulated with at least 25mm of insulation 2 7 5 If applicable Fire Dampers MUST BE FITTED in accordance with Part B of the Building Regulations 2 7 6 Rigid Ducting Install using the fewest nu...

Page 9: ...ch having a minimum contact separation of 3 0mm must be used to provide isolation for the unit 2 8 5 The recommended switches for use with this product are the Zehnder ZGS2 Optional 2 position hardwir...

Page 10: ...speed control via a light switch 2 9 2 Two speed control via ZGS2 switch 2 9 3 Three speed control via ZGS1 switch 2 9 4 Three speed control via a light switch for trickle boost speeds and an AUX spee...

Page 11: ...a minimum separation distance of 35mm between the mains power and controller cables BMS Connector Pre wired supply cord connector DO NOT DISCONNECT ComfoAir 155 CM Figure 9 Top View Cable grommet for...

Page 12: ...e normally closed contact 5 N O Volt Free normally open contact 6 Common Relay common Figure 11 ZGRC1 Controller Figure 12 BMS Wiring Diagram 1 2 3 4 5 6 1 2 6 5 4 3 N C N O COM ELECTRICAL CONNECTION...

Page 13: ...le clamp down with screw fixings 2 9 9 Refit electrical cover taking care gasket seal underneath is seated correctly and cable is not trapped 13 1 2 3 4 5 Pre wired supply cord not shown Figure 13 Sec...

Page 14: ...Bottom line flashing cursor indicating next action to be reviewed changed P O R T C O N F I G R H d w f c k a b Example 2 Re confirmation screen Top line function statement Bottom line three selectab...

Page 15: ...steps of the wizard are as follows 15 P O R T C O N F I G R H E X T R A C T H I G H 6 6 S U P P L Y H I G H 6 6 E X T R A C T L O W 3 3 S U P P L Y L O W 3 3 Port Configuration Set up Rotate button t...

Page 16: ...hoose either ON or OFF Default setting ON Smart Timer Rotate button to choose either ON or OFF Default setting ON Setup Complete Rotate button to EXIT and press button to select Installer Settings 3 1...

Page 17: ...r indicators are NOT reset 3 1 8 Performance Graph Airflow Characteristics S E T U P M E N U p a s s w o r d e n t r y P A S S W O R D X X X X 3 1 9 To Re activate Commissioning Set up Wizard In the e...

Page 18: ...ly Low Wizard airflow setting will be shown rotate button to required airflow Wizard airflow setting will be shown rotate button to required airflow Wizard airflow setting will be shown rotate button...

Page 19: ...Setup Menu Press button to select Enter Password 1010 by rotating the button to the respective number and press to select this has to be completed for each number prior to continuing Rotate button to...

Page 20: ...g to press E OE All goods are sold according to Zehnder s Standard Conditions of Sale which are available on request All dimensions referred to are in millimetres unless otherwise stated Zehnder Group...

Reviews: