20
INSTALLATION
Installation and Servicing
FLUE OUTLET
100mm
Edge of turret
to outside face of wall plus
44mm = flue length
Centre of turret to edge of turret = 100mm
Turret has a flue insertion of 30mm
The compressed outer wall seal has protruding wall to seal mounting lip - 14mm
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
NOTES
REAR
Fit
to wall
A
W
ALL
Edge of turret
to outside face of wall plus
44mm = flue length
Flue length measured from outer terminal lip
to end of outer flue
A
+ 44mm
REAR
Fit
to wall
inc. Stand
off Frame
A
W
ALL
Edge of turret
to outside face of wall plus
44mm = flue length
SIDE
Fit
to wall
A
W
ALL
Minimum clearance 5mm
14
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED, CONT’D
Shows the flue required when measured from outside edge of turret to the outside face of the wall (to obtain cut length add 44mm)
Minimum & Maximum finished flue lengths obtainable (dimension ‘A’ +44mm)
Horizontal Flue Terminal
(600mm long) B Pack
Telescopic Flue B Pack
Horizontal Flue
Terminal (1000mm long)
B Pack (Telescopic)
Horizontal Flue Terminal
(1000mm long) B Pack
(Telescopic) Cut 75mm
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
B Pack (Standard)
171
556
286
484
601
816
526
741
Plus 1 (1m D pack)
1121
1506
1236
1434
1551
1766
1476
1691
Plus 2 (1m D pack)
2071
2456
2186
2384
2501
2716
2426
2641
Plus 3 (1m D pack)
3021
3406
3136
3334
3451
3666
3376
3591
Plus 4 (1m D pack)
3971
4356
4086
4284
4401
4616
4326
4541
Plus 5 (1m D pack)
4921
5306
5036
5234
5351
5566
5276
5491
Plus 6 (1m D pack)
5871
6256
5986
6184
6301
6516
6226
6441
Plus 7 (1m D pack)
6821
7206
6936
7134
7251
7466
7176
7391
Plus 8 (1m D pack)
7771
8186
7886
8084
8201
8416
8126
8341
Plus 9 (1m D pack)
8721
9000
8836
9000
9000
9000
9000
9000
Max output 30 kW
Max output 15, 18 & 24 kW
FIGURE 1
FIGURE 2
Note. Maximum permissible
flue length is measured from
centre line of appliance flue
outlet to outside wall face.
Note; Telescopic flue B Pack or attached “D” pack extensions do not need to be cut between minimum and maximum values
shown above (except where specified). Horizontal Flue Terminal (600mm long) B Pack flue will require cutting on values below
maximum values shown in the table above.
If using the 2000mm D Pack , the maximum usable length per extension is 1950mm
If using the 500mm D Pack, the maximum usable length per extension is 450mm.