Parameters table
DFZ Standard
PSWUTE
4
Password Driver
0
65535
PSWCOST
11
Password Service
0
65535
Regulation parameters
Code
Value
Description
Control cab message
MIN
MAX
UDM
dF1
2,0
Diesel running temperature differential
Diesel differential
1,0/1
10,0/50
°C/°F
dF2
2,0
Stand-by running temperature differential
Electrical standby differential
1,0/1
10,0/50
°C/°F
min
-30,0
Minimum temperature set point
Minimum set point
-50,0/-58
MAS
°C/°F
MAS
25,0
Maximum temperature set point
Maximum set point
Min
50,0/122
°C/°F
Defrosting parameters
Code
Value
Description
Control cab message
MIN
MAX
UDM
tEb
60
Temperature alarm exclusion time after defrosting end
Temp alarm delay
0
999
Minuti
tMS
15
Maximum defrosting time
Maximum duration
1
60
Minuti
tPS
Airs
Defrosting type
Defrost type
probe
clixon
tFS
12,0
Defrosting end temperature
End Defrost Temp.
5,0/41
20,0/68
°C/°F
tSS
120
Time between following defrostings
Defrosts interval
1
999
Minuti
btS
NO
Block of desplayed temperature during defrosting
Temp. Lock
no
si
Flag
tGo
0
Dripping time
Dripping time
0
99
minuti
Svb
OFF
Fans state during defrosting
Fans status
ON
OFF
fl ag
trE
1
Evaporator fans starting delay after defrosting end
Fans delay
0
99
minuti
Alarm parameters
Code
Value
Description
Control cab message
MIN
MAX
UDM
AH
50,0
High temperature alarm
High Temperature
0,0/-58
99,0/210
°C/°F
AL
50,0
Low temperature alarm
Low Temperature
0,0/-58
99,0/210
°C/°F
Ad
2,0
alarm differential?
Alarm Differential
0,0/-58
99,0/122
°C/°F
rAo
15
Oil alarm exclusion time after starting
Oil alarm delay
0
999
Sec
tRA
10
Starting delay after engine water temperature resetting
Reset water alarm
0
999
sec
tRO
10
Starting delay after microdoorswitch alarm resetting
Restart door microswitch
0
999
sec
tAB
10
Starting alarm presence time
Starting Alarm Delay
0
99
Sec
tEr
120
temperature alarm exclusion time after starting
Temp alarm delay
0
999
Minuti
tPO
10
Starting delay after pressure switches and battey alarms resetting Press/batt reset
0
999
sec
tbm
10
Maximum time below minimum tension, allowed before relative
alarm displaying
Low battery delay
0
999
sec
Starting parameters
Code
Value
Description
Control cab message
MIN
MAX
UDM
Vbm
11,0
minimum battery voltage allowed before automatic switching to
continuos running mode
Min. battery voltage
0
20,0
V
Vam
10,0
Minimum alternator voltage allowed during temperature
regulation phase
Reg. alt. Voltage
0
13,0
V
VAM
11,0
Minimum alternator voltage allowed during starting
Starting alt. Voltage
0
13,0
V
VEM
12,0
Minimum alternator voltage allowed during starting and running
in stand-by mode
Electrical alt. Voltage
0
13,0
V
nga
0
Rpm during starting
Starting Rpm
0
5000
100*giri/s
ngf
0
Rpm during regulation
Running Rpm
0
5000
100*giri/s
ngd
0
Rpm difference between the two revolutions counter
Running Rpm
0
5000
100*giri/s
SPr
SI
Pre-heating probe presence
Sensor pre-heating presence
NO
SI
fl ag
tPr
15
Pre-heating time
pre-heating time
0
99
Sec
Ct1M
32
Maximum delay before regulation
Max delay reg.
0
999
sec
Ct1m
12
Minimum delay before regulation
Min delay reg.
0
999
sec
Tmax
60,0
Maximum temperature detectable from water probe
Water Max Temp.
-55,0/-67
11,0/230
°C/°F
Tmin
0,0
Minimum temperature detectable from water probe
Water Min. Temp.
-55,0/-67
11,0/230
°C/°F
Ct1
30
Regulation phase delay after starting
Regulation delay
1
100
Sec
tPA
6
Starting procedure allowable time
Starting process time
1
240
Sec
tmo
0
Minimum running time
Minimum Time
0
999
sec
tPM
5
Starting attempts number
Start attempt
0
10
2.
Parameters table DFZ Standard