background image

ASTRONOMICAL TWO-CHANNELS

TIME PROGRAMMER ZCM-32, ZCM-32P/U

 

INSTRUCTION MANUAL

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: zcm-32_32_pu_bateria_inst_ext_gb | modyfikacja: 25.10.2019

DESCRIPTION

MAIN MENU

APPEARANCE**

OPERATING MODE CHANGE (AUTOMATIC, MANUAL)

STORAGE MODE / BATTERY REPLACEMENT

●  ZCM series programmers have a default setting, the so called storage mode in order to protect the battery during storage.
●  In case of battery backup operation the storage mode is switched off during the first  use of the programmer. It is done by means of a short pressing of the 

 push-button and subsequent date and time adjustment. 

●  In case of a nominal power supply the storage mode is switched off during the first  use of the programmer by means of date and time adjustment.
●  Adjusting the programmer into the storage mode is realised by means of a reset - in order to carry it out press at the same time the   and   push-buttons 

in the main window.

●  ZCM series programmers have the option to replace the clock maintenance battery. Before replacing the battery, disconnect the programmer from the 

external power supply. Please pay the attention to correct battery polarity when replacing.

Description of elements and messages displayed

Button description

   

• In the main window - entry to automatic mode ;

   

• In other windows - one level up exit without saving the introduced data; 

   

• In the main window - entry to manual mode or change of transmitter status if the clock is already in the manual mode;

   

• In other windows - one level up exit without saving the introduced data;

 

  • In the main window - entry to main menu;

   

• In other windows - entry to sub- menu or confirmation of the parameter being set;

 

  • Shifting windows / menu options or increasing / decreasing of the parameter being set; 

   

• Right cursor ( )  in the main window - displaying a time of sunrise and sunset;

   

• Left cursor ( )   in the main window - switching between channels 

 / 

.

We  enter  menu  from  the  main  window  by 

choosing OK; we move inside menu using cur-

sors  . Return to the main window is possible 

after pressing button 

 

or

 

.

You can enter the windows of displaying cal-

culated  sunrise/sunset  time  from  the  main 

window by using cursor  . Return is automat-

ical after 10 s.

  Function Description

 

 

NIGHT BREAK SETTING

 

 

CORRECTION OF TIME SETTING (SUNRISE/ SUNSET TIME)

 

 

CURRENT TIME SETTING

 

 

CURRENT DATE SETTING

 

 

TIME SETTING (SUMMER/WINTER SEASON)

 

  GEOGRAPHICAL POSITION AND TIME ZONE SETTING

 

 

EXTERNAL INPUT SETTING

 

 

EXTERNAL MEMORY ADJUSTMENT**

 

 

CALCULATED SUNRISE TIME

 

 

CALCULATED SUNSET TIME

FEATURES

TECHNICAL DATA

DESCRIPTION

Power supply clamps: A1, A2

Rated voltage: ZCM-32: 230 V AC

~

(-15 ÷ +10 %) 

ZCM-32P/U: 24 ÷ 250 V AC, 30 ÷ 300 V DC

Rated frequency: 50 / 60 Hz

Rated power consumption: 0,8 W / 1,4 VA - stand-by

1,8 W / 3,5 VA - channel 1 and 2 in ON state

 Number of channels: 2

Programme: astronomical (dawn an dusk)

Mode of work: manual, automatic

Change of season summer/ winter: automatic, manual

Colour of LCD panel lighting: amber

Input: yes - independent for the channel 1 and 2

Cooperation with external memory: ZCM-32: no

ZCM-32P/U: yes

Accuracy of time measurement: max. ±1 s / 24  h at temp. 25 °C

Time of clock maintenance: 3 years

Time of programme maintenance: 10 years

Clamps of release system: IN1, IN1 - for channel 1; IN2, IN2 - for channel 2

Clamps of receiver power supply: 11, 12, 14 - channel 1; 21, 22, 24 - channel 2

Parameters of transmitter contacts: 2NO/NC-16 A/250 V AC1 4000 VA

Number of terminating clamps: 12

Intersection of terminating conductors: 0,2 ÷ 2,50 mm

2

Temperature of work: -20 ÷ +60 

o

C

Position of work: any

Fixing of casing: TH 35 rail (PN-EN 60715)

Level of protection of casing: IP20 (PN-EN 60529)

Protectivity class: II

Overvoltage category: II

Level of pollution: 2

Measurements: two-module (35 mm) 90x35x66 mm

Weight: 0,17 kg

Compatibility with norms: PN-EN 60730-1; PN-EN 60730-2-7 

PN-EN 61000-4-2,3,4,5,6,11

●  Steering dependant on a current hour 

in an astronomical cycle,

●  night break programme possibility and 

a change of the calculated sunrise / 

sunset time independently for channel 

1 and 2,

●  two-module casing with a protective 

flap valve,

●  steering inputs IN1, IN2,

●  lighting the LCD display,

●  mounted on TH 35 rail.

Digital steering clocks ZCM-31 are in-

tended for realization of time functions in 

the  systems  of  automatics  and  steering. 

Switching  on/off  the  appliance  is  con-

nected with sunrise and sunset (dawn an 

dusk). The information about geographic 

coordinates, the place of the clock’s instal-

lation, current date and a shift in relation 

to the universal time- all these factors are 

used in order to calculate the time of sun-

rise  and  sunset.  The  system  calculates 

the  end  of  civil  dusk,  that  is  the  phase, 

during which the centre of the Sun’s face 

is located on the 6 degrees angular below 

the horizon- the Sun’s face is not notice-

able but sky is lit with dispersed sunlight. 

The system additionally has a function of 

a  programmed  night  break  and  an  abili-

ty  of  shifting  the  calculated  time  of  sun-

rise and sunset within a range of +/- 120 

min. The construction of a casing makes 

it  possible  to  install  the  system  on  a  rail 

TH 35 and possible sealing the appliance 

with lead. 

The construction of the sys-

tem guarantees supporting of all the 

settings with battery energy when the 

electric power supply is off.

In order to protect the battery during 

storage, the ZCM series programmers 

have a default setting, the so-called 

storage mode in which the battery 

power consumption is limited to a min-

imum.

The  device  should  be  connected  to  a 

singlephase system according to current 

standards.  The  device  connections  will 

be  described  in  this  manual.  Only  qual-

ified  electricians  are  allowed  to  mount, 

connect and adjust the device. It is neces-

sary to read this manual and know the unit 

functions  before  the  device  mounting.  Do  not  disassembly 

the device casing or you will lose any warranty rights and ex-

pose yourself to the electric shock hazard. Before mounting 

operation make sure of disconnecting the connection wires 

from  the  electric  network.  Use  a  cross-head  screwdriver 

of 3.5 mm diameter to mount the device. The relay should 

be carried, stored and used in an appropriate way. Do not 

mount the device in case of any device parts lack, damage 

or deformation. In case of malfunction please notify the man-

ufacturer.

CAUTION

*  does not apply to the product ZCM-32

** apply to the product ZCM-32P/U

*  does not apply to the product ZCM-32

** apply to the product ZCM-32P/U

 

- days of week

 - relay status

 /   - automatic mode / manual

 /   - winter time / summer time

 - external input 

 - day / night 

    

  - channels

 - day

- year

 - night break setting

 - time correction setting

 - current time setting and summer/winter time shift

 - current date setting

 - geographical position setting

 - EXTERNAL INPUT SETTING

 - external memory operation**   

 - external memory record**

 - external memory reading**

 - external memory busy**

 - reading / record error**

 / 

 - sunrise time / sunset time

 / 

 - latitude/ longitude

 - automatic, 

 - user’s

 

 - switched on / switched off

     Before the operating mode changing it is necessary, in the main window, to select with the 

cursors   channel 

  or  

.

 CHANGE OF MODE INTO MANUAL - if the system is situated in the main window and it is 

in the automatic mode, pressing the button   will cause a shift of the system from the manual 

mode with simultaneous change of transmitter status;

 Subsequent pressing of button   will cause switching transmitter to the opposite status with-

out change of work mode;

 CHANGE OF MODE INTO AUTOMATIC - if the system is placed in the main menu and it is in 

the manual mode  , pressing button    will cause automatic shift to the automatic mode, with 

simultaneous updating trans-

mitter status.

    Subsequent  pressing  of 

button    will  cause  switching 

transmitter  to  the  opposite 

status without change of work 

mode.

Winter time

Summer time

Manual mode

Automatic mode

Week’s day

Relay state

Info field:
kanał 1, kanał 2

Current time
(gg:mm:ss)

Power terminals

(A1, A2)

LCD display

External memory**

Replaceable battery

Control buttons

Relay output terminals
(12, 12, 11, 11, 14, 14)

Trigger terminals*

(IN, IN, IN, IN)

Pora: day/noc

Do not dispose of this device with other 

waste! In order to avoid harmful effects 

on the environment and human health, 

the used device should be stored in 

designated areas. For this purpose, you 

can dispose of household waste free of 

charge and in any quantity to a collection 

point set up, as well as to the shop when 

you buy new equipment.

Reviews: