Digital Timers
TR 651 S 

1-channel timer No. 651 0 001

TR 652 S 

2-channel timer No. 652 0 001

TR 653 S 

3-channel timer No. 653 0 001

310 051 01

1.0 Information

The devices TR 651 S – TR 653 S comes ready programmed with the current
time and with the relevant Greenwich mean time rule for automatic sum-
mer / winter timer adjustment.

Should you require a different time adjustment rule, or none at all,

the new

rule can be selected from the table (chapter 

18.2

) and re-programmed as described

in chapter 

18.3

to 

18.6

.

2.0 Application

Time switches switch on, off or over, electrical units time dependent on a day or
week cycle. Time switch TR 651 S, TR 652 S, TR 653 S, is suitable in dry spaces  and
for assembly to the 35 mm top-hait rail (DIN EN 50022). If assembly kit 907 0 050
is used, the  installation can be fitted to a wall.

3.0 Safety information

Electrical devices should only be connected and mounted by an electrical
specialist. The national specifications and applicable safety regulations
must be observed. Manipulations and modifications on the switch will be
result in loss of warranty.

Despite elaborate safety precautions, exceptionally strong electrical fields may cause
interference with the microprocessor-controlled time switch. We therefore recom-
mend that you observe the following points before installation:

• Suppress interference of inductive loads by means of an RC filter

• Use a separate line for the mains voltage suppply

• Do not install device in close proximity to sources of interference, e.g. transfor-

mers, contactors, PCs and TV sets.

• If interference occurs, we recommed that you carry out a RESET before putting

the device back into operation  (press button 

v

C1 

simultaneously).

Attention

This action deletes all stored switching times!

4.0 Features

– free block formation of the weekdays
– 140 memory locations
– holiday program, programmable 21 days in advance for max. 45 days
– Pulse program, 1 – 59 sec., switching times programmable precise to the second.
– 1 x switching e.g. for one time program override on holidays

5.0 Electrical connection

TR 651 S                                                  TR 652 S

TR 653 S

6.0 Technical Data

Operating voltage:

240 V~ + 6 % / – 14 %
230 V~ ± 10 %

Mains frequence:

TR 651 S/652 S

50 – 60 Hz

TR 653 S            

50 Hz

Specified voltage range:

TR 653 S            

60 Hz

Own consumption:

aprox. 7 VA (TR 653 approx. 14 VA)

Contact rating:

TR 651 / 652 S

16 A, 250 V~, cos 

ϕ

 = 1

10 A, 250 V~, cos 

ϕ

 =

0,6

TR 653 S

10 A, 250 V~, cos 

ϕ

 =

1

6 A, 250 V~, cos 

ϕ

 =

0,6 

(Kontakte, potentialfreii)

Kontaktmaterial:

AgSnO

Time base:

quartz

Memory locations:

140

Shortest possible switching interval: 1 minute
Impuls einstellbar:

1 – 59 Sek.

Switching accuracy:

precise-to-the second

Running accuracy:

≤ ±1 sec. / deg at 20 °C

Power reserve:

Lithium max. 8 years at 20 °C

Admissible ambient
temperature:

–10 °C ... +50 °C (-10T50)

Class of protection:

II acc. to  EN 60 335-1 when mounted

Type of enclosure:

IP 20 acc. to EN 60 529

Type:

1 BSTU acc. EN 60730-2-7

Interference suppression degree:
The time switches are in accordance with the  European directives 73/23/EWG Low-
Voltage Directive) and 89/336/EWG (EMC-Directive).
If the time switches are used together with other devices in an installation, take care
that the complete installation does not cause a radio interference.

Dimentioned drawing

7.0 Automatic reset

If no buttons are pressed for a certain length of time in the checking or program-
ming mode, the display is automatically reset to automatic mode after approx.
40 sec. The device then assumes the switching status dictated by the program.

8.0 Setting / changing the current time

Should the time already set in the factory vary slightly, it can be corrected as
follows:
Press button 

v

for approx 1 sec. (see Cursor

under                                   ).

Change the controll-time with button 

h

or 

m

.

Store it by pressing the button 

ENTER

.

9.0 Programming

e. g.

switch C1 Mo – Fr 8.00 (On)

press button  

v

see

Note:

Using the 1 channel timer TR 651 S

Cursor in 

Pos.

the 

key 

is pressed instead of

C1 

or  

C2

.

C1

(On)   >  

Enter

>  

d

Enter 

>  

d

>

Enter

>  

d

Enter 

>  

d

Enter 

>  

h

...

(8  h) > 

Enter

.

e. g.

switch C1 Mo – Fr 18.00 (OFF)

C1 

>  

C1 

(OFF)  >  

Enter

>  

d

Enter 

>  

d

Enter 

d

Enter 

>  

d

Enter 

>  

h

...

(18  h) > 

Enter

.

Pressing the keys 

h

or 

m

for more than 2 

seconds, a fast run – through is carried out.

10. One-time switching

e. g.

one time wednesday 9.45 switch C1 on.

One-time switch has priority

Enter 

(1x) > 

C1 

(On) > 

d

... (3 = We) > 

Enter 

>  

h

... (9 h)  >  

m

> (45 min.) > 

Enter

.

11. Program switching

e. g.

Channel C2 thursday 7:15 switching-on

times

Impuls 10 sec.

C2 

(On)  >  2 x 

d

Enter 

>  

h

(7 h) >

(15 min.) > 

Enter 

m

>  (10 sec.) >

Enter

.

Attention: If you want to program only the switching times of the pulse
program, you must program additional the daily OFF switching times.

12. Pulse program

Switching times can be prolonged by 1 – 59 sec. with an additional On rubbe
command.

C1 

(On)  >  1 x  

d

(Tue)  >  Enter  >  

h

(7 h) 

Enter

C1 

>  

C1

(OFF)  >  1 x  

(Tue)  >  Enter  >

(7 h)  >  

Enter 

>

(25 sec.) >

Enter

.

N

L

N

1 2 3

L

M

N

L

N

1 2 3

4 5 6

L

C 1

C 2

M

N

L

N

1 2 3

4 5 6

7 8

L

C 1

C 2

C 3

M

program display

switch position of
the channels  On, OFF

H   =  holiday program
1 x =  one-time switch

setting of minutes

selection of channel
and ON / OFF

program entry /
recall

time / response time

day indication
e. g. 1 = Monday

2 = Tuesday

setting of weekday

setting of hours

program selector
switch