FUNCTION

FUNCTION

TIMER PROGRAMMING

LOCAL CONTROL - DOUBLE ROLLER BLIND SWITCH

In this mode, short presses (<0.5s) on the corresponding local control switches will cause the SRP-05 controller to perform the following 

operations: opening, closing or stopping a roller blind equipped with a 12 V DC or 24 V DC motor. Roller blind movement time is consistent 

with the time programmed in the controller. The default timer setting is 120 s. After the first press on the local control switch, the roller blind 

moves in the selected direction. After consecutive pressing on any of the local control switches, the roller blind is stopped. Roller blind move-

ment is signaled by the STATUS LED. After a longer pressing on the corresponding local control switch (>2.5s), the controller executes the 

configured comfort settings (lower / upper).

Execution of the upper comfort setting:

To execute the upper comfort setting, completely open the roller blind. Next, press and hold (>2.5s) the local control switch (LOCAL  ). The 

roller blind will start to close and will automatically stop in the programmed upper comfort position.

Execution of the lower comfort setting:

To execute the lower comfort setting, completely close the roller blind. Next, press and hold (>2.5s) the local control switch (LOCAL  ). The 

roller blind will start to open and will automatically stop in the programmed lower comfort position.

LOCAL CONTROL - SINGLE SWITCH

Local control using the single switch is enabled when LOCAL ( ) and LOCAL ( ) inputs are connected.

In this mode, short presses (<0.5s) on the corresponding local control switch will cause the SRP-05 controller to perform the following opera-

tions: opening, closing or stopping a roller blind equipped with a 12 V DC or 24 V DC motor. Roller blind movement time is consistent with the 

time programmed in the controller. The default timer setting is 120 s. Roller blind movement is controlled according to the following sequence: 

open - stop - close. Roller blind movement is signaled by the STATUS LED. After a longer pressing on the local control switch (>2.5s), the 

controller executes the configured comfort settings.

Execution of the upper comfort setting:

To execute the upper comfort setting, completely open the roller blind. Next, press and hold (>2.5s) the local control switch. The roller blind 

will start to close and will automatically stop in the programmed upper comfort position.

Execution of the lower comfort setting:

W celu wywołania ustawienia komfortowego dolnego należy całkowicie zamknąć roletę. Następnie należy dłużej (> 2,5 s) przytrzymać przy-

cisk sterowania lokalnego. Roleta zacznie się otwierać  i automatycznie zatrzyma się w zaprogramowanym położeniu komfortowym dolnym.

NOTE:

The comfort setting timers (for both the upper and lower positions) are the same for the double and single switches. The pro-

grammed roller blind movement time must be longer than the programmed times for the comfort settings. After changing the local 

control mode from the single switch to the double switch, make sure to restart the controller (disconnect from power supply and 

reconnect).

CENTRAL CONTROL - DOUBLE ROLLER BLIND SWITCH ONLY

In this mode, short presses (<0.5s) on the corresponding local control switch will cause the SRP-05 controller to perform the following 

operation: opening and closing a roller blind equipped with a 12 V DC or 24 V DC motor. The roller blind is stopped after the programmed 

roller blind movement time or after pressing any local control switch. The default roller blind movement time is 120 s. if a central command 

is send within this time, causing the roller blind to move in the opposite direction, the roller blind will be stopped and will start moving in the 

opposite direction after about 0.5 s. Roller blind movement is signaled by the STATUS LED.

Central control input locking mode

Central control inputs can lock the roller blind in the closed or open position. For this purpose, signal from the “+” line should be this 

sent to the corresponding CENTRAL ( , ) input. This can be performed, among others, by the alarm unit, the illuminance sensor, the 

precipitation sensor or the control timer. In the locking mode, all other control inputs are disabled. Central control inputs are used for 

long-term release.

Roller blind movement time programming

Roller blind movement time can be programmed from 1s to 10 minutes. This time is common for up and down movement. By default, the 

roller blind movement time is 120 s. Due to mechanical issues, the opening of the roller blind lasts a bit longer than its closing. Therefore, the 

roller blind movement time should be programmed from the lower position (with the roller blind completely closed). The time is saved up to 

the power outage. 

To program the roller blind movement time:

1. Close the roller blind completely.

2. Press the PRÓG button on the SRP-05 controller housing.

3. The roller blind will start to open and time will be measured, which will be signaled with the STATUS LED flashing.

4. When the roller blind reaches its upper position, press any local / central control switch. The roller blind will stop and the movement time 

will be saved in the SRP-05 controller memory.

Programming comfort settings (times)

Comfort setting times can be programmed from 1s to 10 minutes. The upper and lower comfort settings are programmed separately. 

UPPER COMFORT SETTING

To program the upper comfort setting (time):

1. Open the roller blind completely.

2. Press the PRÓG button on the SRP-05 controller housing.

3. The roller blind will start to close and time will be measured, which will be signaled with the STATUS LED flashing.

4. When the roller blind reaches the preset position (upper comfort position), press the PRÓG button on the SRP-05 controller housing again. 

The roller blind will stop and the upper comfort time will be saved in the SRP-05 controller memory.

LOWER COMFORT SETTING

To program the lower comfort setting (time):

1. Close the roller blind completely.

2. Press the PRÓG button on the SRP-05 controller housing.

3. The roller blind will start to open and time will be measured, which will be signaled with the STATUS LED flashing.

4. When the roller blind reaches the preset position (lower comfort position), press the PRÓG button on the SRP-05 controller housing again. 

The roller blind will stop and the lower comfort time will be saved in the SRP-05 controller memory.

To execute a required comfort setting, proceed according to the guidelines for the corresponding control method. 

Comfort setting times are 

saved after a power outage.

Model application:

The ZCM-31 astro-

nomical clock centrally 

closes the window roller 

blind system at dusk. 

Local / central control is 

only enabled at dawn, 

when the 11-14 contacts 

of the clock are opened.

230 V AC

230 V AC

230 V AC

230 V AC

Power Supply

12 V DC

or

24 V DC

Power Supply

12 V DC

or

24 V DC

Power Supply

12 V DC

or

24 V DC

Power Supply

12 V DC

or

24 V DC