background image

plik: inst_ext_gb_rtm-02 | modyfikacja: 03.01.2014

RTM-02 TEMPERATURE REGULATOR 

INSTRUCTION MANUAL

FEATURES

TECHNICAL DATA

DESCRIPTION

APPEARANCE

RTM-02

Power supply terminals: L, N

Input rated voltage: 230 V~

Rated voltage tolerance: -15 ÷ +10 %

Nominal frequency:  50 / 60 Hz

Rated power consumption: 33 mA

Supply voltage indicator: green LED

NTC sensor terminals: IN, IN

Temperature adjustment range: -10°C ÷ +40°C

Hysteresis: ±1 

o

C

Relay terminals: 11, 12, 14

Load supply indicator: red LED

Relay contacts parameters: 16A NO/NC 4000 VA  AC1

Number of terminal clamps:  7

Section of connecting cables:  0,2 ÷ 2,50 mm

2

Ambient temperature range: -20 ÷ 60 

o

C

Operating position: free

Mounting: TH 35 rail (according to PN PN-EN 60715)

Protection degree: IP20 (PN-EN 60529)

Protection level:  II

Overvoltage category: II

Pollution degree: 2

Dimensions: single-module (17,5 mm) 90x17,5x66 mm

Weight: 0,08 kg

Reference standards: PN-EN 60730-1, PN-EN 60730-2-9

PN-EN 61000-4-2,3,4,5,6,11

●  Temperature control in a range of  

-10°C ÷ +40°C,

●  External NTC probe,
●  Power supply indicator,
●  Relay state indicator,
●  Load control in dependence of ambi-

ent temperature,

●  Single-module casing,
●  Mounted on TH 35 rail,
●  Relay output, maximum load 16 A.

The  RTM-02  temperature  regulator  is 

designed  for  load  control  (e.g.  heaters, 

floor heating systems) in dependence of 

ambient  temperature,  near  NTC  sensor. 

The  device  is  capable  of  temperature 

regulating in the range of -10°C ÷ +40°C 

according  to  the  temperature  adjusted 

by  means  of  a  potentiometer  on  the 

unit  front  panel.  The  external  NTC-03 

temperature probe is needed for correct 

system  operation. The  probe  is  not  part 

of the set and it is necessary to purchase 

it  separately.  The  probe  lead  is  3  m  in 

length.  It  is  possible  to  extend  it  up  to  

50 m with 0,2 ÷ 2,5 mm

2

 lead. Do not join 

the probes.

The device is designed for 

single-phase 

installation 

and must be installed in ac-

cordance  with  standards 

valid in a particular country. 

The device should be con-

nected  according  to  the 

details included in this operating manual. 

Installation, connection and control should 

be  carried  out  by  a  qualified  electrician 

staff, who act in accordance with the ser-

vice manual and the device functions. Dis-

assembling  of  the  device  is  equal  with  a 

loss of guarantee and can cause electric 

shock.  Before  installation  make  sure  the 

connection cables are not under voltage. 

The  cruciform  head  screwdriver  3,5  mm 

should  be  used  to  instal  the  device.  Im-

proper transport, storage, and use of the 

device influence its wrong functioning. 

It is not advisable to instal the device in the 

following cases: if any device part is miss-

ing or the device is damaged or deformed. 

In case of improper functioning of the de-

vice contact the producer.

CAUTION

ON threshold setting

Supply voltage indicator

Power terminal (L)

Power terminal (N)

Relay state indicator

Relay output terminals
(11, 12, 14)

Sensor input terminals 

(IN, IN)

NTC probe

The symbol means selective  

collecting of electrical and electronical 

equipment. It is forbidden to put  

the used equipment together  

with other waste

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamelcet.com

, e-mail: [email protected]

Reviews: