Delta Settings
: The Delta T Setting is the delta, or difference between, the setpoint and
current temp for determining when a heat or cool call comes on. The “delta” is the number
of degrees away from setpoint
.
H/C Delta
Range: 3 - 15 degrees.
Default: 3F (1C)
Sets the minimum separation between heating and cooling setpoints. Attempts to lower
the cooling below the heating setpoint by this amount will PUSH the heating setpoint down
to maintain this separation. Same for setting the heating setpoint above the cooling
setpoint, it will PUSH the cooling setpoint up to maintain this separation.
Heating Delta Stage 1 ON
Range: 1 to 8 degrees
Default: 1
Sets the delta from setpoint that stage 1 heating starts.
Heating Delta Stage 1 OFF
Range: 0 to 8 degrees
Default: 0
Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at setpoint
+ Delta Stage 1.
Heating Delta Stage 2 ON
Range: 1 to 8 degrees
Default: 2
Sets the delta from setpoint that stage 2 heating starts.
Heating Delta Stage 2 OFF
Range: 0 to 8 degrees
Default: 0
Sets the delta from setpoint that stage 2 heating stops. Stage 2 turns off at setpoint
+ Delta Stage 2.
Heating Delta Stage 3 ON
Range: 1 to 8 degrees
Default: 3
Sets the delta from setpoint that stage 3 heating starts.
Heating Delta Stage 3 OFF
Range: 0 to 8 degrees
Default: 0
Sets the delta from setpoint that stage 3 heating stops. Stage 3 turns off at setpoint
+ Delta Stage 3.
Cooling Delta Stage 1 ON
Range: 1 to 8 degrees
Default: 1
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Delta Stage 1 OFF
Range: 0 to 8 degrees
Default: 0
Sets the delta from setpoint that stage 1 Cooling stops. Stage 1 turns off at
setpoint - Delta Stage 1
Cooling Delta Stage 2 ON
Range: 1 to 8 degrees
Default: 2
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Delta Stage 2 OFF
Range: 0 to 8 degrees
Default: 0
Sets the delta from setpoint that stage 2 Cooling stops. Stage 2 turns off at
setpoint -Delta Stage 2.
Max Heat SP
Range: 40F to 109F (4C-43C) Default: 90F (32C)
Sets the maximum heating setpoint value. Will not ramp or accept setpoints higher that
this maximum.
Min Cool SP
Range: 44F to 113F (6C-45C) Default: 60F (15C)
Sets the minimum cooling setpoint value. Will not ramp or accept setpoints lower than this
minimum.
Minimum Run Time (MRT)
Range: 1- 9 Minutes
Default: 3
Sets the minimum run time before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid cycling.
Minimum Off Time (MOT)
Range: 5-9 Minutes
Default: 5