Z-Wave T100R Installation Manual Download Page 2

DCN: 140-01773-01

Page 2

INSTALLATION

HVAC System Setup

The thermostat requires that you setup the type and configuration of your HVAC system for 
proper operation.  This is done in the 

Thermostat Info

screen 

Setup

button or the

Installer 

Settings

screen on the thermostat.  The 

Installer Settings

is a hidden screen.  To access it, 

press the main menu button and when the main menu screen appears, press and hold the 
middle two buttons for 5 seconds.  

Thermostat Main Menu

Installer Settings screen

Installer Settings    

Before operating the system, you must configure the thermostat for the correct HVAC 
system type.  You will need to know the following information to correctly configure the 
thermostat.  The HVAC setup is in the 

Mechanical Settings

menu screen.

HVAC system type:

  What type HVAC system do you have? Standard or Heat pump

For Standard systems:

Fan Type:  Do you have Gas heat or Electric heat?   

For Heat Pump systems:

Change over valve (or reversing valve) type:  Does your system 

change over with cooling operation or with heating operation?  Check your existing 

Press and hold two middle buttons to enter the Installer Settings screen

75

Done

Select

Display Lock            N
Service Mode
System Settings
Max Heat SP            90

Installer Settings

+

_

75

Done

Select

User Settings
Away Setpoints
ZWave Install
Thermostat Info

Menu Selection

Summary of Contents for T100R

Page 1: ...System Wiring Terminal Marking Meaning Typical Wire Color Record the old thermostat wire connections and terminal marking here C 24VAC Common Blue R 24VAC Return Red G Fan Green W or W1 Heat stage 1 White Y or Y1 Cool stage 1 Yellow W2 Heat stage 2 Orange Y2 Cool stage 2 Black Heat Pump HVAC System Wiring Terminal Marking Meaning Typical Wire Color Record the old thermostat wire connections and te...

Page 2: ...re the thermostat for the correct HVAC system type You will need to know the following information to correctly configure the thermostat The HVAC setup is in the Mechanical Settings menu screen HVAC system type What type HVAC system do you have Standard or Heat pump For Standard systems Fan Type Do you have Gas heat or Electric heat For Heat Pump systems Change over valve or reversing valve type D...

Page 3: ... system compressor in test mode Disconnect Y1 or Y2 outputs if using test mode on a live system System Settings Submenu Sets the HVAC operational settings below Mechanical Settings Submenu Sets HVAC system type and configuration Type Range Gas Elec or Heat pump Default Gas Elec Selects HVAC type Gas Electric or Heat pump Fan Type Range Gas or Elec Default Gas Selects the Fan type if system is Gas ...

Page 4: ...ge 2 Heating Delta Stage 3 ON Range 1 to 8 degrees Default 3 Sets the delta from setpoint that stage 3 heating starts Heating Delta Stage 3 OFF Range 0 to 8 degrees Default 0 Sets the delta from setpoint that stage 3 heating stops Stage 3 turns off at setpoint Delta Stage 3 Cooling Delta Stage 1 ON Range 1 to 8 degrees Default 1 Sets the delta from setpoint that stage 1 cooling starts Cooling Delt...

Page 5: ...iod followed by an Off period continuously Used to provide minimum air ventilation requirements When the Fan ON time is set to a value greater than 0 an additional Cycler FAN mode is present when pressing the FAN button Fan ON Time Range 0 120 minutes Default 0 OFF Fan OFF Time Range 10 120 minutes Default 10 Restore Defaults Range Yes No Default No Restores all settings to factory defaults Press ...

Page 6: ... 1 On 1 8 1 Cool Delta Stage 1 Off 0 8 0 Cool Delta Stage 2 On 1 8 2 Cool Delta Stage 2 Off 0 8 0 Max Heat SP 40 109F 4 42C 90F Min Cool SP 44 113F 6 45C 60F Min Run Time 1 9 min 3 Min Off Time 1 9 min 5 Temp Response 1 6 2 Fan Cycler Submenu Fan Cycler ON time 0 120 min 0 0 Fan Cycler OFF Fan Cycler Off Time 10 120 min 10 Restore Defaults Yes or No No Exit no USER SETTINGS Filter Service Submenu ...

Page 7: ...used for standard systems Ignore this setting 4 2nd Stage Heat Enable second stage heating outputs If you have a single stage heating system leave this set to N If you have a 2 stage heating system set to Y to enable 5 Aux Heat HP Not used for standard systems Ignore this setting 6 2nd Stage Cool Enable second stage cooling outputs If you have a single stage cooling system leave this set to N If y...

Page 8: ...inal The setting of the C O Type will set the correct system operation For change over with cool systems Orange wire O terminal set C O type to w cool most common and default setting For change over with heat systems Brown wire B terminal set C O type to w heat 4 2nd Stage Heat Enable second stage heating outputs If you have a single stage heating system leave this set to N If you have a 2 stage h...

Reviews: